--  Copyright(C) 2003-2016 Server Technology, Inc.
--

    Sentry4-MIB DEFINITIONS ::= BEGIN

    IMPORTS
        MODULE-IDENTITY, enterprises, Integer32,
        OBJECT-TYPE, NOTIFICATION-TYPE                      FROM SNMPv2-SMI
        OBJECT-GROUP, NOTIFICATION-GROUP, MODULE-COMPLIANCE FROM SNMPv2-CONF
        TEXTUAL-CONVENTION, DisplayString                   FROM SNMPv2-TC;


    sentry4 MODULE-IDENTITY
        LAST-UPDATED "201611182340Z" -- 18 November 2016
        ORGANIZATION "Server Technology, Inc."
        CONTACT-INFO
            "Server Technology, Inc.
             1040 Sandhill Road
             Reno, NV 89521
             Tel: (775) 284-2000
             Fax: (775) 284-2065
             Email: mibmaster@servertech.com"
        DESCRIPTION
            "This is the MIB module for the fourth generation of the
             Sentry product family.  This includes the PRO1 and PRO2
             series of Smart and Switched Cabinet Distribution Unit (CDU)
             and Power Distribution Unit (PDU) products."
        REVISION "201611182340Z" -- 18 November 2016
        DESCRIPTION
            "Added the st4UnitProductMfrDate object.  Adjusted the upper
             limit of voltage objects to 600 Volts."
        REVISION "201609212300Z" -- 21 September 2016
        DESCRIPTION
            "Fixed the st4InputCordOutOfBalanceEvent notification
             definition to include the correct objects."
        REVISION "201604252140Z" -- 25 April 2016
        DESCRIPTION
            "Added support for the PRO1 product series.  Added the
             st4SystemProductSeries and st4InputCordNominalPowerFactor
             objects.  Adjusted the upper limit of cord and line current
             objects to 600 Amps.  Adjusted the lower limit of nominal
             voltage objects to 0 Volts.  Corrected the lower limit of
             several configuration objects from -1 to 0."
        REVISION "201502191000Z" -- 19 February 2015
        DESCRIPTION
            "Corrected the UNITS and value range of temperature sensor
             threshold objects."
        REVISION "201412231130Z" -- 23 December 2014
        DESCRIPTION
            "Initial release."
        ::= { serverTech 4 }

    serverTech OBJECT IDENTIFIER ::= { enterprises 1718 }


--  Common Definitions

    DeviceStatus ::= TEXTUAL-CONVENTION
        STATUS      current
        DESCRIPTION
            "Status returned by devices."
        SYNTAX      INTEGER {
                        normal(0),          -- operating properly
                        disabled(1),        -- disabled
                        purged(2),          -- purged
                        reading(5),         -- read in process
                        settle(6),          -- is settling
                        notFound(7),        -- never connected
                        lost(8),            -- disconnected
                        readError(9),       -- read failure
                        noComm(10),         -- unreachable
                        pwrError(11),       -- power detection error
                        breakerTripped(12), -- breaker error
                        fuseBlown(13),      -- fuse error
                        lowAlarm(14),       -- under low alarm threshold
                        lowWarning(15),     -- under low warning threshold
                        highWarning(16),    -- over high warning threshold
                        highAlarm(17),      -- over high alarm threshold
                        alarm(18),          -- general alarm
                        underLimit(19),     -- under limit alarm
                        overLimit(20),      -- over limit alarm
                        nvmFail(21),        -- NVM failure
                        profileError(22),   -- profile error
                        conflict(23)        -- conflict
                    }

    DeviceState ::= TEXTUAL-CONVENTION
        STATUS      current
        DESCRIPTION
            "On or off state of devices."
        SYNTAX      INTEGER {
                        unknown(0),         -- on / off state is unknown
                        on(1),              -- is on
                        off(2)              -- is off
                    }

    EventNotificationMethods ::= TEXTUAL-CONVENTION
        STATUS      current
        DESCRIPTION
            "Bits to enable event notification methods."
        SYNTAX      BITS {
                        snmpTrap(0),     -- enables notifications by SNMP traps
                        email(1)         -- enables notifications by Email
                    }

--  Object Definitions

    st4Objects OBJECT IDENTIFIER ::= { sentry4 1 }

    -- System

    st4System OBJECT IDENTIFIER ::= { st4Objects 1 }

    -- System Configuration

    st4SystemConfig OBJECT IDENTIFIER ::= { st4System 1 }

    st4SystemProductName OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..63))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The product name."
        ::= { st4SystemConfig 1 }

    st4SystemLocation OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..63))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The location of the system."
        ::= { st4SystemConfig 2 }

    st4SystemFirmwareVersion OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..63))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The firmware version."
        ::= { st4SystemConfig 3 }

    st4SystemFirmwareBuildInfo OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..63))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The firmware build information."
        ::= { st4SystemConfig 4 }

    st4SystemNICSerialNumber OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..8))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The serial number of the network interface card."
        ::= { st4SystemConfig 5 }

    st4SystemNICHardwareInfo OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..63))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Hardware information about the network interface card."
        ::= { st4SystemConfig 6 }

    st4SystemProductSeries OBJECT-TYPE
        SYNTAX      INTEGER {
                        pro1(0),
                        pro2(1)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The product series."
        ::= { st4SystemConfig 7 }

    st4SystemFeatures OBJECT-TYPE
        SYNTAX      BITS {
                        smartLoadShedding(0),
                        reserved(1),
                        outletControlInhibit(2)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The key-activated features enabled in the system."
        ::= { st4SystemConfig 10 }

    st4SystemFeatureKey OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..19))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "A valid feature key written to this object will enable a
             feature in the system.  A valid feature key is in the form
             xxxx-xxxx-xxxx-xxxx.  A read of this object returns an
             empty string."
        ::= { st4SystemConfig 11 }

    st4SystemConfigModifiedCount OBJECT-TYPE
        SYNTAX      Integer32(0..2147483647)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The total number of times the system configuration has changed."
        ::= { st4SystemConfig 20 }

    st4SystemUnitCount OBJECT-TYPE
        SYNTAX      Integer32(0..8)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of units in the system."
        ::= { st4SystemConfig 21 }

    -- Units

    st4Units OBJECT IDENTIFIER ::= { st4Objects 2 }

    -- Unit Common Configuration

    st4UnitCommonConfig OBJECT IDENTIFIER ::= { st4Units 1 }

    -- Unit Configuration Table

    st4UnitConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4UnitConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Unit configuration table."
        ::= { st4Units 2 }

    st4UnitConfigEntry OBJECT-TYPE
        SYNTAX      St4UnitConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular unit."
        INDEX       { st4UnitIndex }
        ::= { st4UnitConfigTable 1 }

    St4UnitConfigEntry ::= SEQUENCE {
        st4UnitIndex                 Integer32,
        st4UnitID                    DisplayString,
        st4UnitName                  DisplayString,
        st4UnitProductSN             DisplayString,
        st4UnitModel                 DisplayString,
        st4UnitAssetTag              DisplayString,
        st4UnitType                  INTEGER,
        st4UnitCapabilities          BITS,
        st4UnitProductMfrDate        DisplayString,
        st4UnitDisplayOrientation    INTEGER,
        st4UnitOutletSequenceOrder   INTEGER,
        st4UnitInputCordCount        Integer32,
        st4UnitTempSensorCount       Integer32,
        st4UnitHumidSensorCount      Integer32,
        st4UnitWaterSensorCount      Integer32,
        st4UnitCcSensorCount         Integer32,
        st4UnitAdcSensorCount        Integer32
    }

    st4UnitIndex OBJECT-TYPE
        SYNTAX      Integer32(1..6)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Unit index.  A=1, B=2, C=3, D=4, E=5, F=6."
        ::= { st4UnitConfigEntry 1 }

    st4UnitID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(1))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the unit.  Format=A."
        ::= { st4UnitConfigEntry 2 }

    st4UnitName OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The name of the unit."
        ::= { st4UnitConfigEntry 3 }

    st4UnitProductSN OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The product serial number of the unit."
        ::= { st4UnitConfigEntry 4 }

    st4UnitModel OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The model of the unit."
        ::= { st4UnitConfigEntry 5 }

    st4UnitAssetTag OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The asset tag of the unit."
        ::= { st4UnitConfigEntry 6 }

    st4UnitType OBJECT-TYPE
        SYNTAX      INTEGER {
                        masterPdu(0),
                        linkPdu(1),
                        controller(2),
                        emcu(3)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The type of the unit."
        ::= { st4UnitConfigEntry 7 }

    st4UnitCapabilities OBJECT-TYPE
        SYNTAX      BITS {
                        dc(0),         -- unit is DC
                        phase3(1),     -- unit is 3 phase
                        wye(2),        -- unit has Wye circuits
                        delta(3)       -- unit has Delta circuits
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The capabilities of the unit."
        ::= { st4UnitConfigEntry 8 }

    st4UnitProductMfrDate OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..10))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The product manufacture date in YYYY-MM-DD (ISO 8601 format)."
        ::= { st4UnitConfigEntry 9 }

    st4UnitDisplayOrientation OBJECT-TYPE
        SYNTAX      INTEGER {
                        normal(0),
                        inverted(1),
                        auto(2)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The orientation of all displays in the unit."
        ::= { st4UnitConfigEntry 20 }

    st4UnitOutletSequenceOrder OBJECT-TYPE
        SYNTAX      INTEGER {
                        normal(0),
                        reversed(1)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The sequencing order of all outlets in the unit."
        ::= { st4UnitConfigEntry 21 }

    st4UnitInputCordCount OBJECT-TYPE
        SYNTAX      Integer32(0..4)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of power input cords into the unit."
        ::= { st4UnitConfigEntry 30 }

    st4UnitTempSensorCount OBJECT-TYPE
        SYNTAX      Integer32(0..2)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of external temperature sensors supported by the unit."
        ::= { st4UnitConfigEntry 31 }

    st4UnitHumidSensorCount OBJECT-TYPE
        SYNTAX      Integer32(0..2)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of external humidity sensors supported by the unit."
        ::= { st4UnitConfigEntry 32 }

    st4UnitWaterSensorCount OBJECT-TYPE
        SYNTAX      Integer32(0..1)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of external water sensors supported by the unit."
        ::= { st4UnitConfigEntry 33 }

    st4UnitCcSensorCount OBJECT-TYPE
        SYNTAX      Integer32(0..4)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of external contact closure sensors supported by the
             unit."
        ::= { st4UnitConfigEntry 34 }

    st4UnitAdcSensorCount OBJECT-TYPE
        SYNTAX      Integer32(0..1)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of analog-to-digital converter sensors supported by the
             unit."
        ::= { st4UnitConfigEntry 35 }

    -- Unit Monitor Table

    st4UnitMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4UnitMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Unit monitor table."
        ::= { st4Units 3 }

    st4UnitMonitorEntry OBJECT-TYPE
        SYNTAX      St4UnitMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular unit."
        INDEX       { st4UnitIndex }
        ::= { st4UnitMonitorTable 1 }

    St4UnitMonitorEntry ::= SEQUENCE {
        st4UnitStatus                 DeviceStatus
    }

    st4UnitStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the unit."
        ::= { st4UnitMonitorEntry 1 }

    -- Unit Event Configuration Table

    st4UnitEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4UnitEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Unit event configuration table."
        ::= { st4Units 4 }

    st4UnitEventConfigEntry OBJECT-TYPE
        SYNTAX      St4UnitEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular unit."
        INDEX       { st4UnitIndex }
        ::= { st4UnitEventConfigTable 1 }

    St4UnitEventConfigEntry ::= SEQUENCE {
        st4UnitNotifications              EventNotificationMethods
    }

    st4UnitNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for unit events."
        ::= { st4UnitEventConfigEntry 1 }

    -- Input Cords

    st4InputCords OBJECT IDENTIFIER ::= { st4Objects 3 }

    -- Input Cord Common Configuration

    st4InputCordCommonConfig OBJECT IDENTIFIER ::= { st4InputCords 1 }

    st4InputCordActivePowerHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..1000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The active power hysteresis of the input cord in Watts."
        ::= { st4InputCordCommonConfig 1 }

    st4InputCordApparentPowerHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..1000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The apparent power hysteresis of the input cord in Volt-Amps."
        ::= { st4InputCordCommonConfig 2 }

    st4InputCordPowerFactorHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..20)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The power factor hysteresis of the input cord in hundredths."
        ::= { st4InputCordCommonConfig 3 }

    st4InputCordOutOfBalanceHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..10)
        UNITS       "percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 3 phase out-of-balance hysteresis of the input cord in
             percent."
        ::= { st4InputCordCommonConfig 4 }

    -- Input Cord Configuration Table

    st4InputCordConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4InputCordConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Input cord configuration table."
        ::= { st4InputCords 2 }

    st4InputCordConfigEntry OBJECT-TYPE
        SYNTAX      St4InputCordConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular input cord."
        INDEX       { st4UnitIndex, st4InputCordIndex }
        ::= { st4InputCordConfigTable 1 }

    St4InputCordConfigEntry ::= SEQUENCE {
        st4InputCordIndex                 Integer32,
        st4InputCordID                    DisplayString,
        st4InputCordName                  DisplayString,
        st4InputCordInletType             DisplayString,
        st4InputCordNominalVoltage        Integer32,
        st4InputCordNominalVoltageMin     Integer32,
        st4InputCordNominalVoltageMax     Integer32,
        st4InputCordCurrentCapacity       Integer32,
        st4InputCordCurrentCapacityMax    Integer32,
        st4InputCordPowerCapacity         Integer32,
        st4InputCordNominalPowerFactor    Integer32,
        st4InputCordLineCount             Integer32,
        st4InputCordPhaseCount            Integer32,
        st4InputCordOcpCount              Integer32,
        st4InputCordBranchCount           Integer32,
        st4InputCordOutletCount           Integer32
    }

    st4InputCordIndex OBJECT-TYPE
        SYNTAX      Integer32(1..4)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Input cord index.  A=1, B=2, C=3, D=4."
        ::= { st4InputCordConfigEntry 1 }

    st4InputCordID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(2))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the input cord.  Format=AA."
        ::= { st4InputCordConfigEntry 2 }

    st4InputCordName OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The name of the input cord."
        ::= { st4InputCordConfigEntry 3 }

    st4InputCordInletType OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The type of plug on the input cord, or socket for the input cord."
        ::= { st4InputCordConfigEntry 6}

    st4InputCordNominalVoltage OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Volts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The user-configured nominal voltage of the input cord in tenth
             Volts."
        ::= { st4InputCordConfigEntry 7 }

    st4InputCordNominalVoltageMin OBJECT-TYPE
        SYNTAX      Integer32(0..600)
        UNITS       "Volts"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The factory-set minimum allowed for the user-configured nominal
             voltage of the input cord in Volts."
        ::= { st4InputCordConfigEntry 8 }

    st4InputCordNominalVoltageMax OBJECT-TYPE
        SYNTAX      Integer32(0..600)
        UNITS       "Volts"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The factory-set maximum allowed for the user-configured nominal
             voltage of the input cord in Volts."
        ::= { st4InputCordConfigEntry 9 }

    st4InputCordCurrentCapacity OBJECT-TYPE
        SYNTAX      Integer32(0..600)
        UNITS       "Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The user-configured current capacity of the input cord in Amps."
        ::= { st4InputCordConfigEntry 10 }

    st4InputCordCurrentCapacityMax OBJECT-TYPE
        SYNTAX      Integer32(0..600)
        UNITS       "Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The factory-set maximum allowed for the user-configured current
             capacity of the input cord in Amps."
        ::= { st4InputCordConfigEntry 11 }

    st4InputCordPowerCapacity OBJECT-TYPE
        SYNTAX      Integer32(0..50000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The power capacity of the input cord in Volt-Amps.  For DC
             products, this is identical to power capacity in Watts."
        ::= { st4InputCordConfigEntry 12 }

    st4InputCordNominalPowerFactor OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The user-configured estimated nominal power factor of the input
             cord in hundredths."
        ::= { st4InputCordConfigEntry 13 }

    st4InputCordLineCount OBJECT-TYPE
        SYNTAX      Integer32(0..4)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of current-carrying lines in the input cord."
        ::= { st4InputCordConfigEntry 20 }

    st4InputCordPhaseCount OBJECT-TYPE
        SYNTAX      Integer32(0..6)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of active phases from the lines in the input cord."
        ::= { st4InputCordConfigEntry 21 }

    st4InputCordOcpCount OBJECT-TYPE
        SYNTAX      Integer32(0..12)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of over-current protectors downstream from the input
             cord."
        ::= { st4InputCordConfigEntry 22 }

    st4InputCordBranchCount OBJECT-TYPE
        SYNTAX      Integer32(0..12)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of branches downstream from the input cord."
        ::= { st4InputCordConfigEntry 23 }

    st4InputCordOutletCount OBJECT-TYPE
        SYNTAX      Integer32(0..128)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of outlets powered from the input cord."
        ::= { st4InputCordConfigEntry 24 }

    -- Input Cord Monitor Table

    st4InputCordMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4InputCordMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Input cord monitor table."
        ::= { st4InputCords 3 }

    st4InputCordMonitorEntry OBJECT-TYPE
        SYNTAX      St4InputCordMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular input cord."
        INDEX       { st4UnitIndex, st4InputCordIndex }
        ::= { st4InputCordMonitorTable 1 }

    St4InputCordMonitorEntry ::= SEQUENCE {
        st4InputCordState                  DeviceState,
        st4InputCordStatus                 DeviceStatus,
        st4InputCordActivePower            Integer32,
        st4InputCordActivePowerStatus      DeviceStatus,
        st4InputCordApparentPower          Integer32,
        st4InputCordApparentPowerStatus    DeviceStatus,
        st4InputCordPowerUtilized          Integer32,
        st4InputCordPowerFactor            Integer32,
        st4InputCordPowerFactorStatus      DeviceStatus,
        st4InputCordEnergy                 Integer32,
        st4InputCordFrequency              Integer32,
        st4InputCordOutOfBalance           Integer32,
        st4InputCordOutOfBalanceStatus     DeviceStatus
    }

    st4InputCordState OBJECT-TYPE
        SYNTAX      DeviceState
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The on/off state of the input cord."
        ::= { st4InputCordMonitorEntry 1 }

    st4InputCordStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the input cord."
        ::= { st4InputCordMonitorEntry 2 }

    st4InputCordActivePower OBJECT-TYPE
        SYNTAX      Integer32(-1..50000)
        UNITS       "Watts"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured active power of the input cord in Watts."
        ::= { st4InputCordMonitorEntry 3 }

    st4InputCordActivePowerStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured active power of the input cord."
        ::= { st4InputCordMonitorEntry 4 }

    st4InputCordApparentPower OBJECT-TYPE
        SYNTAX      Integer32(-1..50000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured apparent power of the input cord in Volt-Amps."
        ::= { st4InputCordMonitorEntry 5 }

    st4InputCordApparentPowerStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured apparent power of the input cord."
        ::= { st4InputCordMonitorEntry 6 }

    st4InputCordPowerUtilized OBJECT-TYPE
        SYNTAX      Integer32(-1..1200)
        UNITS       "tenth percent"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The amount of the input cord power capacity used in tenth percent.
             For AC products, this is the ratio of the apparent power to the
             power capacity.  For DC products, this is the ratio of the active
             power to the power capacity."
        ::= { st4InputCordMonitorEntry 7 }

    st4InputCordPowerFactor OBJECT-TYPE
        SYNTAX      Integer32(-1..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured power factor of the input cord in hundredths."
        ::= { st4InputCordMonitorEntry 8 }

    st4InputCordPowerFactorStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured power factor of the input cord."
        ::= { st4InputCordMonitorEntry 9 }

    st4InputCordEnergy OBJECT-TYPE
        SYNTAX      Integer32(-1..2147483647)
        UNITS       "tenth Kilowatt-Hours"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The total energy consumption of loads through the input cord in
             tenth Kilowatt-Hours."
        ::= { st4InputCordMonitorEntry 10 }

    st4InputCordFrequency OBJECT-TYPE
        SYNTAX      Integer32(-1..1000)
        UNITS       "tenth Hertz"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The frequency of the input cord voltage in tenth Hertz."
        ::= { st4InputCordMonitorEntry 11 }

    st4InputCordOutOfBalance OBJECT-TYPE
        SYNTAX      Integer32(-1..2000)
        UNITS       "tenth percent"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The current imbalance on the lines of the input cord in tenth
             percent."
        ::= { st4InputCordMonitorEntry 12 }

    st4InputCordOutOfBalanceStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the current imbalance on the lines of the input
             cord."
        ::= { st4InputCordMonitorEntry 13 }

    -- Input Cord Event Configuration Table

    st4InputCordEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4InputCordEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Input cord event configuration table."
        ::= { st4InputCords 4 }

    st4InputCordEventConfigEntry OBJECT-TYPE
        SYNTAX      St4InputCordEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular input cord."
        INDEX       { st4UnitIndex, st4InputCordIndex }
        ::= { st4InputCordEventConfigTable 1 }

    St4InputCordEventConfigEntry ::= SEQUENCE {
        st4InputCordNotifications              EventNotificationMethods,
        st4InputCordActivePowerLowAlarm        Integer32,
        st4InputCordActivePowerLowWarning      Integer32,
        st4InputCordActivePowerHighWarning     Integer32,
        st4InputCordActivePowerHighAlarm       Integer32,
        st4InputCordApparentPowerLowAlarm      Integer32,
        st4InputCordApparentPowerLowWarning    Integer32,
        st4InputCordApparentPowerHighWarning   Integer32,
        st4InputCordApparentPowerHighAlarm     Integer32,
        st4InputCordPowerFactorLowAlarm        Integer32,
        st4InputCordPowerFactorLowWarning      Integer32,
        st4InputCordOutOfBalanceHighWarning    Integer32,
        st4InputCordOutOfBalanceHighAlarm      Integer32
    }

    st4InputCordNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for input cord events."
        ::= { st4InputCordEventConfigEntry 1 }

    st4InputCordActivePowerLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..50000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The active power low alarm threshold of the input cord in Watts."
        ::= { st4InputCordEventConfigEntry 2 }

    st4InputCordActivePowerLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..50000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The active power low warning threshold of the input cord in
             Watts."
        ::= { st4InputCordEventConfigEntry 3 }

    st4InputCordActivePowerHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..50000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The active power high warning threshold of the input cord in
             Watts."
        ::= { st4InputCordEventConfigEntry 4 }

    st4InputCordActivePowerHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..50000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The active power high alarm threshold of the input cord in Watts."
        ::= { st4InputCordEventConfigEntry 5 }

    st4InputCordApparentPowerLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..50000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The apparent power low alarm threshold of the input cord in
             Volt-Amps."
        ::= { st4InputCordEventConfigEntry 6 }

    st4InputCordApparentPowerLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..50000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The apparent power low warning threshold of the input cord in
             Volt-Amps."
        ::= { st4InputCordEventConfigEntry 7 }

    st4InputCordApparentPowerHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..50000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The apparent power high warning threshold of the input cord in
             Volt-Amps."
        ::= { st4InputCordEventConfigEntry 8 }

    st4InputCordApparentPowerHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..50000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The apparent power high alarm threshold of the input cord in
             Volt-Amps."
        ::= { st4InputCordEventConfigEntry 9 }

    st4InputCordPowerFactorLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The power factor low alarm threshold of the input cord in
             hundredths."
        ::= { st4InputCordEventConfigEntry 10 }

    st4InputCordPowerFactorLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The power factor low warning threshold of the input cord in
             hundredths."
        ::= { st4InputCordEventConfigEntry 11 }

    st4InputCordOutOfBalanceHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 3 phase out-of-balance high warning threshold of the input
             cord in percent."
        ::= { st4InputCordEventConfigEntry 12 }

    st4InputCordOutOfBalanceHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 3 phase out-of-balance high alarm threshold of the input cord
             in percent."
        ::= { st4InputCordEventConfigEntry 13 }

    -- Lines

    st4Lines OBJECT IDENTIFIER ::= { st4Objects 4 }

    -- Line Common Configuration

    st4LineCommonConfig OBJECT IDENTIFIER ::= { st4Lines 1 }

    st4LineCurrentHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current hysteresis of the line in tenth Amps."
        ::= { st4LineCommonConfig 1 }

    -- Line Configuration Table

    st4LineConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4LineConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Line configuration table."
        ::= { st4Lines 2 }

    st4LineConfigEntry OBJECT-TYPE
        SYNTAX      St4LineConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular line."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4LineIndex }
        ::= { st4LineConfigTable 1 }

    St4LineConfigEntry ::= SEQUENCE {
        st4LineIndex                 Integer32,
        st4LineID                    DisplayString,
        st4LineLabel                 DisplayString,
        st4LineCurrentCapacity       Integer32
    }

    st4LineIndex OBJECT-TYPE
        SYNTAX      Integer32(1..4)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Line index.  L1=1, L2=2, L3=3, N=4."
        ::= { st4LineConfigEntry 1 }

    st4LineID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the line.  Format=AAN."
        ::= { st4LineConfigEntry 2 }

    st4LineLabel OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The system label assigned to the line for identification."
        ::= { st4LineConfigEntry 4 }

    st4LineCurrentCapacity OBJECT-TYPE
        SYNTAX      Integer32(0..600)
        UNITS       "Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The current capacity of the line in Amps."
        ::= { st4LineConfigEntry 6 }

    -- Line Monitor Table

    st4LineMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4LineMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Line monitor table."
        ::= { st4Lines 3 }

    st4LineMonitorEntry OBJECT-TYPE
        SYNTAX      St4LineMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular line."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4LineIndex }
        ::= { st4LineMonitorTable 1 }

    St4LineMonitorEntry ::= SEQUENCE {
        st4LineState                  DeviceState,
        st4LineStatus                 DeviceStatus,
        st4LineCurrent                Integer32,
        st4LineCurrentStatus          DeviceStatus,
        st4LineCurrentUtilized        Integer32
    }

    st4LineState OBJECT-TYPE
        SYNTAX      DeviceState
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The on/off state of the line."
        ::= { st4LineMonitorEntry 1 }

    st4LineStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the line."
        ::= { st4LineMonitorEntry 2 }

    st4LineCurrent OBJECT-TYPE
        SYNTAX      Integer32(-1..60000)
        UNITS       "hundredth Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured current on the line in hundredth Amps."
        ::= { st4LineMonitorEntry 3 }

    st4LineCurrentStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured current on the line."
        ::= { st4LineMonitorEntry 4 }

    st4LineCurrentUtilized OBJECT-TYPE
        SYNTAX      Integer32(-1..1200)
        UNITS       "tenth percent"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The amount of the line current capacity used in tenth percent."
        ::= { st4LineMonitorEntry 5 }

    -- Line Event Configuration Table

    st4LineEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4LineEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Line event configuration table."
        ::= { st4Lines 4 }

    st4LineEventConfigEntry OBJECT-TYPE
        SYNTAX      St4LineEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular line."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4LineIndex }
        ::= { st4LineEventConfigTable 1 }

    St4LineEventConfigEntry ::= SEQUENCE {
        st4LineNotifications              EventNotificationMethods,
        st4LineCurrentLowAlarm            Integer32,
        st4LineCurrentLowWarning          Integer32,
        st4LineCurrentHighWarning         Integer32,
        st4LineCurrentHighAlarm           Integer32
    }

    st4LineNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for line events."
        ::= { st4LineEventConfigEntry 1 }

    st4LineCurrentLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current low alarm threshold of the line in tenth Amps."
        ::= { st4LineEventConfigEntry 2 }

    st4LineCurrentLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current low warning threshold of the line in tenth Amps."
        ::= { st4LineEventConfigEntry 3 }

    st4LineCurrentHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current high warning threshold of the line in tenth Amps."
        ::= { st4LineEventConfigEntry 4 }

    st4LineCurrentHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current high alarm threshold of the line in tenth Amps."
        ::= { st4LineEventConfigEntry 5 }

    -- Phases

    st4Phases OBJECT IDENTIFIER ::= { st4Objects 5 }

    -- Phase Common Configuration

    st4PhaseCommonConfig OBJECT IDENTIFIER ::= { st4Phases 1 }

    st4PhaseVoltageHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..200)
        UNITS       "tenth Volts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The voltage hysteresis of the phase in tenth Volts."
        ::= { st4PhaseCommonConfig 1 }

    st4PhasePowerFactorHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..20)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The power factor hysteresis of the phase in hundredths."
        ::= { st4PhaseCommonConfig 2 }

    -- Phase Configuration Table

    st4PhaseConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4PhaseConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Phase configuration table."
        ::= { st4Phases 2 }

    st4PhaseConfigEntry OBJECT-TYPE
        SYNTAX      St4PhaseConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular phase."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4PhaseIndex }
        ::= { st4PhaseConfigTable 1 }

    St4PhaseConfigEntry ::= SEQUENCE {
        st4PhaseIndex                 Integer32,
        st4PhaseID                    DisplayString,
        st4PhaseLabel                 DisplayString,
        st4PhaseNominalVoltage        Integer32,
        st4PhaseBranchCount           Integer32,
        st4PhaseOutletCount           Integer32
    }

    st4PhaseIndex OBJECT-TYPE
        SYNTAX      Integer32(1..6)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Phase index.  Three-phase AC Wye: L1-N=1, L2-N=2, L3-N=3;
             Three-phase AC Delta: L1-L2=1, L2-L3=2, L3-L1=3; Single Phase:
             L1-R=1; DC: L1-R=1; Three-phase AC Wye & Delta: L1-N=1, L2-N=2,
             L3-N=3, L1-L2=4, L2-L3=5; L3-L1=6."
        ::= { st4PhaseConfigEntry 1 }

    st4PhaseID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the phase.  Format=AAN."
        ::= { st4PhaseConfigEntry 2 }

    st4PhaseLabel OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The system label assigned to the phase for identification."
        ::= { st4PhaseConfigEntry 4 }

    st4PhaseNominalVoltage OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Volts"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The nominal voltage of the phase in tenth Volts."
        ::= { st4PhaseConfigEntry 6 }

    st4PhaseBranchCount OBJECT-TYPE
        SYNTAX      Integer32(0..12)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of branches downstream from the phase."
        ::= { st4PhaseConfigEntry 20 }

    st4PhaseOutletCount OBJECT-TYPE
        SYNTAX      Integer32(0..128)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of outlets powered from the phase."
        ::= { st4PhaseConfigEntry 21 }

    -- Phase Monitor Table

    st4PhaseMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4PhaseMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Phase monitor table."
        ::= { st4Phases 3 }

    st4PhaseMonitorEntry OBJECT-TYPE
        SYNTAX      St4PhaseMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular phase."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4PhaseIndex }
        ::= { st4PhaseMonitorTable 1 }

    St4PhaseMonitorEntry ::= SEQUENCE {
        st4PhaseState                  DeviceState,
        st4PhaseStatus                 DeviceStatus,
        st4PhaseVoltage                Integer32,
        st4PhaseVoltageStatus          DeviceStatus,
        st4PhaseVoltageDeviation       Integer32,
        st4PhaseCurrent                Integer32,
        st4PhaseCurrentCrestFactor     Integer32,
        st4PhaseActivePower            Integer32,
        st4PhaseApparentPower          Integer32,
        st4PhasePowerFactor            Integer32,
        st4PhasePowerFactorStatus      DeviceStatus,
        st4PhaseReactance              Integer32,
        st4PhaseEnergy                 Integer32
    }

    st4PhaseState OBJECT-TYPE
        SYNTAX      DeviceState
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The on/off state of the phase."
        ::= { st4PhaseMonitorEntry 1 }

    st4PhaseStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the phase."
        ::= { st4PhaseMonitorEntry 2 }

    st4PhaseVoltage OBJECT-TYPE
        SYNTAX      Integer32(-1..6000)
        UNITS       "tenth Volts"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured voltage on the phase in tenth Volts."
        ::= { st4PhaseMonitorEntry 3 }

    st4PhaseVoltageStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured voltage on the phase."
        ::= { st4PhaseMonitorEntry 4 }

    st4PhaseVoltageDeviation OBJECT-TYPE
        SYNTAX      Integer32(-1000..1000)
        UNITS       "tenth percent"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The deviation from the nominal voltage on the phase in tenth
             percent."
        ::= { st4PhaseMonitorEntry 5 }

    st4PhaseCurrent OBJECT-TYPE
        SYNTAX      Integer32(-1..30000)
        UNITS       "hundredth Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured current on the phase in hundredth Amps."
        ::= { st4PhaseMonitorEntry 6 }

    st4PhaseCurrentCrestFactor OBJECT-TYPE
        SYNTAX      Integer32(-1..250)
        UNITS       "tenths"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured crest factor of the current waveform on the phase in
             tenths."
        ::= { st4PhaseMonitorEntry 7 }

    st4PhaseActivePower OBJECT-TYPE
        SYNTAX      Integer32(-1..25000)
        UNITS       "Watts"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured active power on the phase in Watts."
        ::= { st4PhaseMonitorEntry 8 }

    st4PhaseApparentPower OBJECT-TYPE
        SYNTAX      Integer32(-1..25000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured apparent power on the phase in Volt-Amps."
        ::= { st4PhaseMonitorEntry 9 }

    st4PhasePowerFactor OBJECT-TYPE
        SYNTAX      Integer32(-1..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured power factor on the phase in hundredths."
        ::= { st4PhaseMonitorEntry 10 }

    st4PhasePowerFactorStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured power factor on the phase."
        ::= { st4PhaseMonitorEntry 11 }

    st4PhaseReactance OBJECT-TYPE
        SYNTAX      INTEGER {
                        unknown(0),
                        capacitive(1),
                        inductive(2),
                        resistive(3)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured reactance of the phase."
        ::= { st4PhaseMonitorEntry 12 }

    st4PhaseEnergy OBJECT-TYPE
        SYNTAX      Integer32(-1..2147483647)
        UNITS       "tenth Kilowatt-Hours"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The total energy consumption of loads through the phase in tenth
             Kilowatt-Hours."
        ::= { st4PhaseMonitorEntry 13 }

    -- Phase Event Configuration Table

    st4PhaseEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4PhaseEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Phase event configuration table."
        ::= { st4Phases 4 }

    st4PhaseEventConfigEntry OBJECT-TYPE
        SYNTAX      St4PhaseEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular phase."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4PhaseIndex }
        ::= { st4PhaseEventConfigTable 1 }

    St4PhaseEventConfigEntry ::= SEQUENCE {
        st4PhaseNotifications              EventNotificationMethods,
        st4PhaseVoltageLowAlarm            Integer32,
        st4PhaseVoltageLowWarning          Integer32,
        st4PhaseVoltageHighWarning         Integer32,
        st4PhaseVoltageHighAlarm           Integer32,
        st4PhasePowerFactorLowAlarm        Integer32,
        st4PhasePowerFactorLowWarning      Integer32
    }

    st4PhaseNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for phase events."
        ::= { st4PhaseEventConfigEntry 1 }

    st4PhaseVoltageLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Volts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current low alarm threshold of the phase in tenth Volts."
        ::= { st4PhaseEventConfigEntry 2 }

    st4PhaseVoltageLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Volts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current low warning threshold of the phase in tenth Volts."
        ::= { st4PhaseEventConfigEntry 3 }

    st4PhaseVoltageHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Volts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current high warning threshold of the phase in tenth Volts."
        ::= { st4PhaseEventConfigEntry 4 }

    st4PhaseVoltageHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..6000)
        UNITS       "tenth Volts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current high alarm threshold of the phase in tenth Volts."
        ::= { st4PhaseEventConfigEntry 5 }

    st4PhasePowerFactorLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low power factor alarm threshold of the phase in hundredths."
        ::= { st4PhaseEventConfigEntry 6 }

    st4PhasePowerFactorLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low power factor warning threshold of the phase in
             hundredths."
        ::= { st4PhaseEventConfigEntry 7 }

    -- Over-Current Protectors

    st4OverCurrentProtectors OBJECT IDENTIFIER ::= { st4Objects 6 }

    -- Over-Current Protector Common Configuration

    st4OcpCommonConfig OBJECT IDENTIFIER ::= { st4OverCurrentProtectors 1 }

    -- Over-Current Protector Configuration Table

    st4OcpConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4OcpConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Over-current protector configuration table."
        ::= { st4OverCurrentProtectors 2 }

    st4OcpConfigEntry OBJECT-TYPE
        SYNTAX      St4OcpConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular over-current protector."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4OcpIndex }
        ::= { st4OcpConfigTable 1 }

    St4OcpConfigEntry ::= SEQUENCE {
        st4OcpIndex                 Integer32,
        st4OcpID                    DisplayString,
        st4OcpLabel                 DisplayString,
        st4OcpType                  INTEGER,
        st4OcpCurrentCapacity       Integer32,
        st4OcpCurrentCapacityMax    Integer32,
        st4OcpBranchCount           Integer32,
        st4OcpOutletCount           Integer32
    }

    st4OcpIndex OBJECT-TYPE
        SYNTAX      Integer32(1..64)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Over-current protector index."
        ::= { st4OcpConfigEntry 1 }

    st4OcpID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3..4))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the over-current protector.  Format=AAN[N]."
        ::= { st4OcpConfigEntry 2 }

    st4OcpLabel OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The system label assigned to the over-current protector for
             identification."
        ::= { st4OcpConfigEntry 4 }

    st4OcpType OBJECT-TYPE
        SYNTAX      INTEGER {
                        fuse(0),
                        breaker(1)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The type of over-current protector."
        ::= { st4OcpConfigEntry 6 }

    st4OcpCurrentCapacity OBJECT-TYPE
        SYNTAX      Integer32(0..125)
        UNITS       "Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The user-configured current capacity of the over-current protector
             in Amps."
        ::= { st4OcpConfigEntry 7 }

    st4OcpCurrentCapacityMax OBJECT-TYPE
        SYNTAX      Integer32(0..125)
        UNITS       "Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The factory-set maximum allowed for the user-configured current
             capacity of the over-current protector in Amps."
        ::= { st4OcpConfigEntry 8 }

    st4OcpBranchCount OBJECT-TYPE
        SYNTAX      Integer32(0..12)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of branches downstream from the over-current
             protector."
        ::= { st4OcpConfigEntry 20 }

    st4OcpOutletCount OBJECT-TYPE
        SYNTAX      Integer32(0..128)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of outlets powered from the over-current protector."
        ::= { st4OcpConfigEntry 21 }

    -- Over-Current Protector Monitor Table

    st4OcpMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4OcpMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Over-current protector monitor table."
        ::= { st4OverCurrentProtectors 3 }

    st4OcpMonitorEntry OBJECT-TYPE
        SYNTAX      St4OcpMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular over-current protector."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4OcpIndex }
        ::= { st4OcpMonitorTable 1 }

    St4OcpMonitorEntry ::= SEQUENCE {
        st4OcpStatus                 DeviceStatus
    }

    st4OcpStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the over-current protector."
        ::= { st4OcpMonitorEntry 1 }

    -- Over-Current Protector Event Configuration Table

    st4OcpEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4OcpEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Over-current protector event configuration table."
        ::= { st4OverCurrentProtectors 4 }

    st4OcpEventConfigEntry OBJECT-TYPE
        SYNTAX      St4OcpEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular over-current
             protector."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4OcpIndex }
        ::= { st4OcpEventConfigTable 1 }

    St4OcpEventConfigEntry ::= SEQUENCE {
        st4OcpNotifications              EventNotificationMethods
    }

    st4OcpNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for over-current protector
             events."
        ::= { st4OcpEventConfigEntry 1 }

    -- Branches

    st4Branches OBJECT IDENTIFIER ::= { st4Objects 7 }

    -- Branch Common Configuration

    st4BranchCommonConfig OBJECT IDENTIFIER ::= { st4Branches 1 }

    st4BranchCurrentHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current hysteresis of the branch in tenth Amps."
        ::= { st4BranchCommonConfig 1 }

    -- Branch Configuration Table

    st4BranchConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4BranchConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Branch configuration table."
        ::= { st4Branches 2 }

    st4BranchConfigEntry OBJECT-TYPE
        SYNTAX      St4BranchConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular branch."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4BranchIndex }
        ::= { st4BranchConfigTable 1 }

    St4BranchConfigEntry ::= SEQUENCE {
        st4BranchIndex                 Integer32,
        st4BranchID                    DisplayString,
        st4BranchLabel                 DisplayString,
        st4BranchCurrentCapacity       Integer32,
        st4BranchPhaseID               DisplayString,
        st4BranchOcpID                 DisplayString,
        st4BranchOutletCount           Integer32
    }

    st4BranchIndex OBJECT-TYPE
        SYNTAX      Integer32(1..64)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Branch index."
        ::= { st4BranchConfigEntry 1 }

    st4BranchID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3..4))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the branch.  Format=AAN[N]."
        ::= { st4BranchConfigEntry 2 }

    st4BranchLabel OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The system label assigned to the branch for identification."
        ::= { st4BranchConfigEntry 4 }

    st4BranchCurrentCapacity OBJECT-TYPE
        SYNTAX      Integer32(0..125)
        UNITS       "Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The current capacity of the branch in Amps."
        ::= { st4BranchConfigEntry 6 }

    st4BranchPhaseID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the phase powering this branch.
             Format=AAN."
        ::= { st4BranchConfigEntry 20 }

    st4BranchOcpID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3..4))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the over-current protector powering this
             outlet.  Format=AAN[N]."
        ::= { st4BranchConfigEntry 21 }

    st4BranchOutletCount OBJECT-TYPE
        SYNTAX      Integer32(0..128)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of outlets powered from the branch."
        ::= { st4BranchConfigEntry 30 }

    -- Branch Monitor Table

    st4BranchMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4BranchMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Branch monitor table."
        ::= { st4Branches 3 }

    st4BranchMonitorEntry OBJECT-TYPE
        SYNTAX      St4BranchMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular branch."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4BranchIndex }
        ::= { st4BranchMonitorTable 1 }

    St4BranchMonitorEntry ::= SEQUENCE {
        st4BranchState                  DeviceState,
        st4BranchStatus                 DeviceStatus,
        st4BranchCurrent                Integer32,
        st4BranchCurrentStatus          DeviceStatus,
        st4BranchCurrentUtilized        Integer32
    }

    st4BranchState OBJECT-TYPE
        SYNTAX      DeviceState
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The on/off state of the branch."
        ::= { st4BranchMonitorEntry 1 }

    st4BranchStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the branch."
        ::= { st4BranchMonitorEntry 2 }

    st4BranchCurrent OBJECT-TYPE
        SYNTAX      Integer32(-1..12500)
        UNITS       "hundredth Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured current on the branch in hundredth Amps."
        ::= { st4BranchMonitorEntry 3 }

    st4BranchCurrentStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured current on the branch."
        ::= { st4BranchMonitorEntry 4 }

    st4BranchCurrentUtilized OBJECT-TYPE
        SYNTAX      Integer32(-1..1200)
        UNITS       "tenth percent"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The amount of the branch current capacity used in tenth percent."
        ::= { st4BranchMonitorEntry 5 }

    -- Branch Event Configuration Table

    st4BranchEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4BranchEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Branch event configuration table."
        ::= { st4Branches 4 }

    st4BranchEventConfigEntry OBJECT-TYPE
        SYNTAX      St4BranchEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular branch."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4BranchIndex }
        ::= { st4BranchEventConfigTable 1 }

    St4BranchEventConfigEntry ::= SEQUENCE {
        st4BranchNotifications              EventNotificationMethods,
        st4BranchCurrentLowAlarm            Integer32,
        st4BranchCurrentLowWarning          Integer32,
        st4BranchCurrentHighWarning         Integer32,
        st4BranchCurrentHighAlarm           Integer32
    }

    st4BranchNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for branch events."
        ::= { st4BranchEventConfigEntry 1 }

    st4BranchCurrentLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..1250)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current low alarm threshold of the branch in tenth Amps."
        ::= { st4BranchEventConfigEntry 2 }

    st4BranchCurrentLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..1250)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current low warning threshold of the branch in tenth Amps."
        ::= { st4BranchEventConfigEntry 3 }

    st4BranchCurrentHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..1250)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current high warning threshold of the branch in tenth Amps."
        ::= { st4BranchEventConfigEntry 4 }

    st4BranchCurrentHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..1250)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current high alarm threshold of the branch in tenth Amps."
        ::= { st4BranchEventConfigEntry 5 }

    -- Outlets

    st4Outlets OBJECT IDENTIFIER ::= { st4Objects 8 }

    -- Outlet Common Configuration

    st4OutletCommonConfig OBJECT IDENTIFIER ::= { st4Outlets 1 }

    st4OutletCurrentHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current hysteresis of the outlet in tenth Amps."
        ::= { st4OutletCommonConfig 1 }

    st4OutletActivePowerHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..1000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The power hysteresis of the outlet in Watts."
        ::= { st4OutletCommonConfig 2 }

    st4OutletPowerFactorHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..20)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The power factor hysteresis of the outlet in hundredths."
        ::= { st4OutletCommonConfig 3 }

    st4OutletSequenceInterval OBJECT-TYPE
        SYNTAX      Integer32(0..15)
        UNITS       "seconds"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The power-on sequencing interval for all outlets in seconds."
        ::= { st4OutletCommonConfig 10 }

    st4OutletRebootDelay OBJECT-TYPE
        SYNTAX      Integer32(5..600)
        UNITS       "seconds"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The reboot delay for all outlets in seconds."
        ::= { st4OutletCommonConfig 11 }

    st4OutletStateChangeLogging OBJECT-TYPE
        SYNTAX      INTEGER {
                        disabled(0),
                        enabled(1)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Enables or disables informational Outlet State Change event
             logging."
        ::= { st4OutletCommonConfig 12 }

    -- Outlet Configuration Table

    st4OutletConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4OutletConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Outlet configuration table."
        ::= { st4Outlets 2 }

    st4OutletConfigEntry OBJECT-TYPE
        SYNTAX      St4OutletConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular outlet."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
        ::= { st4OutletConfigTable 1 }

    St4OutletConfigEntry ::= SEQUENCE {
        st4OutletIndex                 Integer32,
        st4OutletID                    DisplayString,
        st4OutletName                  DisplayString,
        st4OutletCapabilities          BITS,
        st4OutletSocketType            DisplayString,
        st4OutletCurrentCapacity       Integer32,
        st4OutletPowerCapacity         Integer32,
        st4OutletWakeupState           INTEGER,
        st4OutletPostOnDelay           Integer32,
        st4OutletPhaseID               DisplayString,
        st4OutletOcpID                 DisplayString,
        st4OutletBranchID              DisplayString
    }

    st4OutletIndex OBJECT-TYPE
        SYNTAX      Integer32(1..128)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Outlet index."
        ::= { st4OutletConfigEntry 1 }

    st4OutletID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3..5))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the outlet.  Format=AAN[N[N]]."
        ::= { st4OutletConfigEntry 2 }

    st4OutletName OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The name of the outlet."
        ::= { st4OutletConfigEntry 3 }

    st4OutletCapabilities OBJECT-TYPE
        SYNTAX      BITS {
                          switched(0),         -- outlet supports power control
                          pops(1)              -- outlet has pops
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The capabilities of the outlet."
        ::= { st4OutletConfigEntry 5 }

    st4OutletSocketType OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The socket type of the outlet."
        ::= { st4OutletConfigEntry 6 }

    st4OutletCurrentCapacity OBJECT-TYPE
        SYNTAX      Integer32(0..125)
        UNITS       "Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The current capacity of the outlet in Amps."
        ::= { st4OutletConfigEntry 7 }

    st4OutletPowerCapacity OBJECT-TYPE
        SYNTAX      Integer32(0..10000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The power capacity of the outlet in Volt-Amps.  For DC products,
             this is identical to power capacity in Watts."
        ::= { st4OutletConfigEntry 8 }

    st4OutletWakeupState OBJECT-TYPE
        SYNTAX      INTEGER {
                        on(0),
                        off(1),
                        last(2)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The wakeup state of the outlet."
        ::= { st4OutletConfigEntry 20 }

    st4OutletPostOnDelay OBJECT-TYPE
        SYNTAX      Integer32(0..900)
        UNITS       "seconds"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The post-on delay of the outlet in seconds."
        ::= { st4OutletConfigEntry 21 }

    st4OutletPhaseID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the phase powering this outlet.
             Format=AAN."
        ::= { st4OutletConfigEntry 30 }

    st4OutletOcpID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3..4))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the over-current protector powering this
             outlet.  Format=AAN[N]."
        ::= { st4OutletConfigEntry 31 }

    st4OutletBranchID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(3..4))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the branch powering this outlet.
             Format=AAN[N]."
        ::= { st4OutletConfigEntry 32 }

    -- Outlet Monitor Table

    st4OutletMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4OutletMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Outlet monitor table."
        ::= { st4Outlets 3 }

    st4OutletMonitorEntry OBJECT-TYPE
        SYNTAX      St4OutletMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular outlet."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
        ::= { st4OutletMonitorTable 1 }

    St4OutletMonitorEntry ::= SEQUENCE {
        st4OutletState                  DeviceState,
        st4OutletStatus                 DeviceStatus,
        st4OutletCurrent                Integer32,
        st4OutletCurrentStatus          DeviceStatus,
        st4OutletCurrentUtilized        Integer32,
        st4OutletVoltage                Integer32,
        st4OutletActivePower            Integer32,
        st4OutletActivePowerStatus      DeviceStatus,
        st4OutletApparentPower          Integer32,
        st4OutletPowerFactor            Integer32,
        st4OutletPowerFactorStatus      DeviceStatus,
        st4OutletCurrentCrestFactor     Integer32,
        st4OutletReactance              INTEGER,
        st4OutletEnergy                 Integer32
    }

    st4OutletState OBJECT-TYPE
        SYNTAX      DeviceState
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The on/off state of the outlet."
        ::= { st4OutletMonitorEntry 1 }

    st4OutletStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the outlet."
        ::= { st4OutletMonitorEntry 2 }

    st4OutletCurrent OBJECT-TYPE
        SYNTAX      Integer32(-1..12500)
        UNITS       "hundredth Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured current on the outlet in hundredth Amps."
        ::= { st4OutletMonitorEntry 3 }

    st4OutletCurrentStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured current on the outlet."
        ::= { st4OutletMonitorEntry 4 }

    st4OutletCurrentUtilized OBJECT-TYPE
        SYNTAX      Integer32(-1..1200)
        UNITS       "tenth percent"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
           "The amount of the outlet current capacity used in tenth percent."
        ::= { st4OutletMonitorEntry 5 }

    st4OutletVoltage OBJECT-TYPE
        SYNTAX      Integer32(-1..6000)
        UNITS       "tenth Volts"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured voltage of the outlet in tenth Volts."
        ::= { st4OutletMonitorEntry 6 }

    st4OutletActivePower OBJECT-TYPE
        SYNTAX      Integer32(-1..10000)
        UNITS       "Watts"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured active power of the outlet in Watts."
        ::= { st4OutletMonitorEntry 7 }

    st4OutletActivePowerStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured active power of the outlet."
        ::= { st4OutletMonitorEntry 8 }

    st4OutletApparentPower OBJECT-TYPE
        SYNTAX      Integer32(-1..10000)
        UNITS       "Volt-Amps"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured apparent power of the outlet in Volt-Amps."
        ::= { st4OutletMonitorEntry 9 }

    st4OutletPowerFactor OBJECT-TYPE
        SYNTAX      Integer32(-1..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured power factor of the outlet in hundredths."
        ::= { st4OutletMonitorEntry 10 }

    st4OutletPowerFactorStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured power factor of the outlet."
        ::= { st4OutletMonitorEntry 11 }

    st4OutletCurrentCrestFactor OBJECT-TYPE
        SYNTAX      Integer32(-1..250)
        UNITS       "tenths"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured crest factor of the outlet in tenths."
        ::= { st4OutletMonitorEntry 12 }

    st4OutletReactance OBJECT-TYPE
        SYNTAX      INTEGER {
                        unknown(0),
                        capacitive(1),
                        inductive(2),
                        resistive(3)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the measured reactance of the outlet."
        ::= { st4OutletMonitorEntry 13 }

    st4OutletEnergy OBJECT-TYPE
        SYNTAX      Integer32(-1..2147483647)
        UNITS       "Watt-Hours"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The total energy consumption of the device plugged into the outlet
             in Watt-Hours."
        ::= { st4OutletMonitorEntry 14 }

    -- Outlet Event Configuration Table

    st4OutletEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4OutletEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Outlet event configuration table."
        ::= { st4Outlets 4 }

    st4OutletEventConfigEntry OBJECT-TYPE
        SYNTAX      St4OutletEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular outlet."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
        ::= { st4OutletEventConfigTable 1 }

    St4OutletEventConfigEntry ::= SEQUENCE {
        st4OutletNotifications              EventNotificationMethods,
        st4OutletCurrentLowAlarm            Integer32,
        st4OutletCurrentLowWarning          Integer32,
        st4OutletCurrentHighWarning         Integer32,
        st4OutletCurrentHighAlarm           Integer32,
        st4OutletActivePowerLowAlarm        Integer32,
        st4OutletActivePowerLowWarning      Integer32,
        st4OutletActivePowerHighWarning     Integer32,
        st4OutletActivePowerHighAlarm       Integer32,
        st4OutletPowerFactorLowAlarm        Integer32,
        st4OutletPowerFactorLowWarning      Integer32
    }

    st4OutletNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for outlet events."
        ::= { st4OutletEventConfigEntry 1 }

    st4OutletCurrentLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..1250)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current low alarm threshold of the outlet in tenth Amps."
        ::= { st4OutletEventConfigEntry 2 }

    st4OutletCurrentLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..1250)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current low warning threshold of the outlet in tenth Amps."
        ::= { st4OutletEventConfigEntry 3 }

    st4OutletCurrentHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..1250)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current high warning threshold of the outlet in tenth Amps."
        ::= { st4OutletEventConfigEntry 4 }

    st4OutletCurrentHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..1250)
        UNITS       "tenth Amps"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current high alarm threshold of the outlet in tenth Amps."
        ::= { st4OutletEventConfigEntry 5 }

    st4OutletActivePowerLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..10000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The active power low alarm threshold of the outlet in Watts."
        ::= { st4OutletEventConfigEntry 6 }

    st4OutletActivePowerLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..10000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The active power low warning threshold of the outlet in Watts."
        ::= { st4OutletEventConfigEntry 7 }

    st4OutletActivePowerHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..10000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The active power high warning threshold of the outlet in Watts."
        ::= { st4OutletEventConfigEntry 8 }

    st4OutletActivePowerHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..10000)
        UNITS       "Watts"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The active power high alarm threshold of the outlet in Watts."
        ::= { st4OutletEventConfigEntry 9 }

    st4OutletPowerFactorLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low power factor alarm threshold of the outlet in hundredths."
        ::= { st4OutletEventConfigEntry 10 }

    st4OutletPowerFactorLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "hundredths"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low power factor warning threshold of the outlet in
             hundredths."
        ::= { st4OutletEventConfigEntry 11 }

    -- Outlet Control Table

    st4OutletControlTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4OutletControlEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Outlet control table."
        ::= { st4Outlets 5 }

    st4OutletControlEntry OBJECT-TYPE
        SYNTAX      St4OutletControlEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects for control of a particular outlet."
        INDEX       { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
        ::= { st4OutletControlTable 1 }

    St4OutletControlEntry ::= SEQUENCE {
        st4OutletControlState           INTEGER,
        st4OutletControlAction          INTEGER
    }

    st4OutletControlState OBJECT-TYPE
        SYNTAX      INTEGER {
                        notSet(0),         -- outlet state is unknown
                        fixedOn(1),        -- outlet is uncontrolled (assumed on)
                        idleOff(2),        -- outlet has defaulted to off state
                        idleOn(3),         -- outlet has defaulted to on state
                        wakeOff(4),        -- outlet has been set to off by wakeup
                        wakeOn(5),         -- outlet has been set to on by wakeup
                        ocpOff(6),         -- outlet is off due to OCP failure
                        ocpOn(7),          -- outlet had OCP power loss
                        pendOn(8),         -- outlet is off, but will be turning on
                        pendOff(9),        -- outlet is on, but will be turning off
                        off(10),           -- outlet was turned off by user
                        on(11),            -- outlet was turned on by user or reboot event
                        reboot(12),        -- outlet is preparing to turn on
                        shutdown(13),      -- outlet is preparing to turn off
                        lockedOff(14),     -- outlet was locked off by admin
                        lockedOn(15),      -- outlet was locked on by admin
                        eventOff(16),      -- outlet was turned off by an event
                        eventOn(17),       -- outlet was turned on by an event
                        eventReboot(18),   -- outlet rebooting due to an event
                        eventShutdown(19)  -- outlet shutting down due to an event
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The control state of the outlet."
        ::= { st4OutletControlEntry 1 }

    st4OutletControlAction OBJECT-TYPE
        SYNTAX      INTEGER {
                        none(0),
                        on(1),
                        off(2),
                        reboot(3),
                        queueOn(4),
                        queueOff(5),
                        queueReboot(6)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "An action to change the control state of the outlet, or to queue
             an action."
        ::= { st4OutletControlEntry 2 }

    -- Outlet Common Control

    st4OutletCommonControl OBJECT IDENTIFIER ::= { st4Outlets 6 }

    st4OutletQueueControl OBJECT-TYPE
        SYNTAX      INTEGER {
                        clear(0),
                        commit(1)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "An action to clear or commit queued outlet control actions.  A
             read of this object returns clear(0) if queue is empty, and
             commit(1) if the queue is not empty."
        ::= { st4OutletCommonControl 1 }

    -- Temperature Sensors

    st4TemperatureSensors OBJECT IDENTIFIER ::= { st4Objects 9 }

    -- Temperature Sensor Common Configuration

    st4TempSensorCommonConfig OBJECT IDENTIFIER ::= { st4TemperatureSensors 1 }

    st4TempSensorHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..54)
        UNITS       "degrees"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The temperature hysteresis of the sensor in degrees, using the
             scale selected by st4TempSensorScale."
        ::= { st4TempSensorCommonConfig 1 }

    st4TempSensorScale OBJECT-TYPE
        SYNTAX      INTEGER {
                        celsius(0),
                        fahrenheit(1)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The current scale used for all temperature values."
        ::= { st4TempSensorCommonConfig 10 }

    -- Temperature Sensor Configuration Table

    st4TempSensorConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4TempSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Temperature sensor configuration table."
        ::= { st4TemperatureSensors 2 }

    st4TempSensorConfigEntry OBJECT-TYPE
        SYNTAX      St4TempSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular temperature sensor."
        INDEX       { st4UnitIndex, st4TempSensorIndex }
        ::= { st4TempSensorConfigTable 1 }

    St4TempSensorConfigEntry ::= SEQUENCE {
        st4TempSensorIndex                 Integer32,
        st4TempSensorID                    DisplayString,
        st4TempSensorName                  DisplayString,
        st4TempSensorValueMin              Integer32, 
        st4TempSensorValueMax              Integer32 
    }

    st4TempSensorIndex OBJECT-TYPE
        SYNTAX      Integer32(0..2)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Temperature sensor index."
        ::= { st4TempSensorConfigEntry 1 }

    st4TempSensorID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(2))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the temperature sensor.  Format=AN."
        ::= { st4TempSensorConfigEntry 2 }

    st4TempSensorName OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The name of the temperature sensor."
        ::= { st4TempSensorConfigEntry 3 }

    st4TempSensorValueMin OBJECT-TYPE
        SYNTAX      Integer32(-40..253)
        UNITS       "degrees"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The minimum temperature limit of the sensor in degrees, using the
             scale selected by st4TempSensorScale."
        ::= { st4TempSensorConfigEntry 4 }

    st4TempSensorValueMax OBJECT-TYPE
        SYNTAX      Integer32(-40..253)
        UNITS       "degrees"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The maximum temperature limit of the sensor in degrees, using the
             scale selected by st4TempSensorScale."
        ::= { st4TempSensorConfigEntry 5 }

    -- Temperature Sensor Monitor Table

    st4TempSensorMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4TempSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Temperature sensor monitor table."
        ::= { st4TemperatureSensors 3 }

    st4TempSensorMonitorEntry OBJECT-TYPE
        SYNTAX      St4TempSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular temperature sensor."
        INDEX       { st4UnitIndex, st4TempSensorIndex }
        ::= { st4TempSensorMonitorTable 1 }

    St4TempSensorMonitorEntry ::= SEQUENCE {
        st4TempSensorValue                  Integer32,
        st4TempSensorStatus                 DeviceStatus
    }

    st4TempSensorValue OBJECT-TYPE
        SYNTAX      Integer32(-410..2540)
        UNITS       "tenth degrees"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured temperature on the sensor in tenth degrees using the
             scale selected by st4TempSensorScale. -410 means the temperature
             reading is invalid."
        ::= { st4TempSensorMonitorEntry 1 }

    st4TempSensorStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the temperature sensor."
        ::= { st4TempSensorMonitorEntry 2 }

    -- Temperature Sensor Event Configuration Table

    st4TempSensorEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4TempSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Temperature sensor event configuration table."
        ::= { st4TemperatureSensors 4 }

    st4TempSensorEventConfigEntry OBJECT-TYPE
        SYNTAX      St4TempSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular temperature sensor."
        INDEX       { st4UnitIndex, st4TempSensorIndex }
        ::= { st4TempSensorEventConfigTable 1 }

    St4TempSensorEventConfigEntry ::= SEQUENCE {
        st4TempSensorNotifications              EventNotificationMethods,
        st4TempSensorLowAlarm                   Integer32,
        st4TempSensorLowWarning                 Integer32,
        st4TempSensorHighWarning                Integer32,
        st4TempSensorHighAlarm                  Integer32
    }

    st4TempSensorNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for temperature sensor events."
        ::= { st4TempSensorEventConfigEntry 1 }

    st4TempSensorLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(-40..253)
        UNITS       "degrees"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low alarm threshold of the temperature sensor in degrees."
        ::= { st4TempSensorEventConfigEntry 2 }

    st4TempSensorLowWarning OBJECT-TYPE
        SYNTAX      Integer32(-40..253)
        UNITS       "degrees"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low warning threshold of the temperature sensor in degrees."
        ::= { st4TempSensorEventConfigEntry 3 }

    st4TempSensorHighWarning OBJECT-TYPE
        SYNTAX      Integer32(-40..253)
        UNITS       "degrees"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The high warning threshold of the temperature sensor in degrees."
        ::= { st4TempSensorEventConfigEntry 4 }

    st4TempSensorHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(-40..253)
        UNITS       "degrees"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The high alarm threshold of the temperature sensor in degrees."
        ::= { st4TempSensorEventConfigEntry 5 }

    -- Humidity Sensors

    st4HumiditySensors OBJECT IDENTIFIER ::= { st4Objects 10 }

    -- Humidity Sensor Common Configuration

    st4HumidSensorCommonConfig OBJECT IDENTIFIER ::= { st4HumiditySensors 1 }

    st4HumidSensorHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..20)
        UNITS       "percentage relative humidity"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The humidity hysteresis of the sensor in percent relative
             humidity."
        ::= { st4HumidSensorCommonConfig 1 }

    -- Humidity Sensor Configuration Table

    st4HumidSensorConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4HumidSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Humidity sensor configuration table."
        ::= { st4HumiditySensors 2 }

    st4HumidSensorConfigEntry OBJECT-TYPE
        SYNTAX      St4HumidSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular humidity sensor."
        INDEX       { st4UnitIndex, st4HumidSensorIndex }
        ::= { st4HumidSensorConfigTable 1 }

    St4HumidSensorConfigEntry ::= SEQUENCE {
        st4HumidSensorIndex                 Integer32,
        st4HumidSensorID                    DisplayString,
        st4HumidSensorName                  DisplayString
    }

    st4HumidSensorIndex OBJECT-TYPE
        SYNTAX      Integer32(0..2)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Humidity sensor index."
        ::= { st4HumidSensorConfigEntry 1 }

    st4HumidSensorID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(2))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the humidity sensor.  Format=AN."
        ::= { st4HumidSensorConfigEntry 2 }

    st4HumidSensorName OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The name of the humidity sensor."
        ::= { st4HumidSensorConfigEntry 3 }

    -- Humidity Sensor Monitor Table

    st4HumidSensorMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4HumidSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Humidity sensor monitor table."
        ::= { st4HumiditySensors 3 }

    st4HumidSensorMonitorEntry OBJECT-TYPE
        SYNTAX      St4HumidSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular humidity sensor."
        INDEX       { st4UnitIndex, st4HumidSensorIndex }
        ::= { st4HumidSensorMonitorTable 1 }

    St4HumidSensorMonitorEntry ::= SEQUENCE {
        st4HumidSensorValue                  Integer32,
        st4HumidSensorStatus                 DeviceStatus
    }

    st4HumidSensorValue OBJECT-TYPE
        SYNTAX      Integer32(-1..100)
        UNITS       "percentage relative humidity"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured humidity on the sensor in percentage relative
             humidity."
        ::= { st4HumidSensorMonitorEntry 1 }

    st4HumidSensorStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the humidity sensor."
        ::= { st4HumidSensorMonitorEntry 2 }

    -- Humidity Sensor Event Configuration Table

    st4HumidSensorEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4HumidSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Humidity sensor event configuration table."
        ::= { st4HumiditySensors 4 }

    st4HumidSensorEventConfigEntry OBJECT-TYPE
        SYNTAX      St4HumidSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular humidity sensor."
        INDEX       { st4UnitIndex, st4HumidSensorIndex }
        ::= { st4HumidSensorEventConfigTable 1 }

    St4HumidSensorEventConfigEntry ::= SEQUENCE {
        st4HumidSensorNotifications              EventNotificationMethods,
        st4HumidSensorLowAlarm                   Integer32,
        st4HumidSensorLowWarning                 Integer32,
        st4HumidSensorHighWarning                Integer32,
        st4HumidSensorHighAlarm                  Integer32
    }

    st4HumidSensorNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for humidity sensor events."
        ::= { st4HumidSensorEventConfigEntry 1 }

    st4HumidSensorLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "percentage relative humidity"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low alarm threshold of the humidity sensor in percentage
             relative humidity."
        ::= { st4HumidSensorEventConfigEntry 2 }

    st4HumidSensorLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "percentage relative humidity"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low warning threshold of the humidity sensor in percentage
             relative humidity."
        ::= { st4HumidSensorEventConfigEntry 3 }

    st4HumidSensorHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "percentage relative humidity"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The high warning threshold of the humidity sensor in percentage
             relative humidity."
        ::= { st4HumidSensorEventConfigEntry 4 }

    st4HumidSensorHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..100)
        UNITS       "percentage relative humidity"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The high alarm threshold of the humidity sensor in percentage
             relative humidity."
        ::= { st4HumidSensorEventConfigEntry 5 }

    -- Water Sensors

    st4WaterSensors OBJECT IDENTIFIER ::= { st4Objects 11 }

    -- Water Sensor Common Configuration

    st4WaterSensorCommonConfig OBJECT IDENTIFIER ::= { st4WaterSensors 1 }

    -- Water Sensor Configuration Table

    st4WaterSensorConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4WaterSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Water sensor configuration table."
        ::= { st4WaterSensors 2 }

    st4WaterSensorConfigEntry OBJECT-TYPE
        SYNTAX      St4WaterSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular water sensor."
        INDEX       { st4UnitIndex, st4WaterSensorIndex }
        ::= { st4WaterSensorConfigTable 1 }

    St4WaterSensorConfigEntry ::= SEQUENCE {
        st4WaterSensorIndex                 Integer32,       
        st4WaterSensorID                    DisplayString,
        st4WaterSensorName                  DisplayString
    }

    st4WaterSensorIndex OBJECT-TYPE
        SYNTAX      Integer32(0..1)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Water sensor index."
        ::= { st4WaterSensorConfigEntry 1 }

    st4WaterSensorID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(2))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the water sensor.  Format=AN."
        ::= { st4WaterSensorConfigEntry 2 }

    st4WaterSensorName OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The name of the water sensor."
        ::= { st4WaterSensorConfigEntry 3 }

    -- Water Sensor Monitor Table

    st4WaterSensorMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4WaterSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Water sensor monitor table."
        ::= { st4WaterSensors 3 }

    st4WaterSensorMonitorEntry OBJECT-TYPE
        SYNTAX      St4WaterSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular water sensor."
        INDEX       { st4UnitIndex, st4WaterSensorIndex }
        ::= { st4WaterSensorMonitorTable 1 }

    St4WaterSensorMonitorEntry ::= SEQUENCE {
        st4WaterSensorStatus                 DeviceStatus
    }

    st4WaterSensorStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the water sensor."
        ::= { st4WaterSensorMonitorEntry 1 }

    -- Water Sensor Event Configuration Table

    st4WaterSensorEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4WaterSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Water sensor event configuration table."
        ::= { st4WaterSensors 4 }

    st4WaterSensorEventConfigEntry OBJECT-TYPE
        SYNTAX      St4WaterSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular water sensor."
        INDEX       { st4UnitIndex, st4WaterSensorIndex }
        ::= { st4WaterSensorEventConfigTable 1 }

    St4WaterSensorEventConfigEntry ::= SEQUENCE {
        st4WaterSensorNotifications              EventNotificationMethods
    }

    st4WaterSensorNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for water sensor events."
        ::= { st4WaterSensorEventConfigEntry 1 }

    -- Contact Closures Sensors

    st4ContactClosureSensors OBJECT IDENTIFIER ::= { st4Objects 12 }

    -- Contact Closure Sensor Common Configuration

    st4CcSensorCommonConfig OBJECT IDENTIFIER ::= { st4ContactClosureSensors 1 }

    -- Contact Closure Sensor Configuration Table

    st4CcSensorConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4CcSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Contact closure sensor configuration table."
        ::= { st4ContactClosureSensors 2 }

    st4CcSensorConfigEntry OBJECT-TYPE
        SYNTAX      St4CcSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular contact closure sensor."
        INDEX       { st4UnitIndex, st4CcSensorIndex }
        ::= { st4CcSensorConfigTable 1 }

    St4CcSensorConfigEntry ::= SEQUENCE {
        st4CcSensorIndex                 Integer32,       
        st4CcSensorID                    DisplayString,
        st4CcSensorName                  DisplayString
    }

    st4CcSensorIndex OBJECT-TYPE
        SYNTAX      Integer32(0..4)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Contact closure sensor index."
        ::= { st4CcSensorConfigEntry 1 }

    st4CcSensorID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(2))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the contact closure sensor.  Format=AN."
        ::= { st4CcSensorConfigEntry 2 }

    st4CcSensorName OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The name of the contact closure sensor."
        ::= { st4CcSensorConfigEntry 3 }

    -- Contact Closure Sensor Monitor Table

    st4CcSensorMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4CcSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Contact closure sensor monitor table."
        ::= { st4ContactClosureSensors 3 }

    st4CcSensorMonitorEntry OBJECT-TYPE
        SYNTAX      St4CcSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular contact closure sensor."
        INDEX       { st4UnitIndex, st4CcSensorIndex }
        ::= { st4CcSensorMonitorTable 1 }

    St4CcSensorMonitorEntry ::= SEQUENCE {
        st4CcSensorStatus                 DeviceStatus
    }

    st4CcSensorStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the contact closure."
        ::= { st4CcSensorMonitorEntry 1 }

    -- Contact Closure Sensor Event Configuration Table

    st4CcSensorEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4CcSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Contact closure sensor event configuration table."
        ::= { st4ContactClosureSensors 4 }

    st4CcSensorEventConfigEntry OBJECT-TYPE
        SYNTAX      St4CcSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular contact closure
             sensor."
        INDEX       { st4UnitIndex, st4CcSensorIndex }
        ::= { st4CcSensorEventConfigTable 1 }

    St4CcSensorEventConfigEntry ::= SEQUENCE {
        st4CcSensorNotifications              EventNotificationMethods
    }

    st4CcSensorNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for contact closure sensor
             events."
        ::= { st4CcSensorEventConfigEntry 1 }

    -- Analog-to-Digital Converter Sensors

    st4AnalogToDigitalConvSensors OBJECT IDENTIFIER ::= { st4Objects 13 }

    -- Analog-to-Digital Converter Sensor Common Configuration

    st4AdcSensorCommonConfig OBJECT IDENTIFIER ::= { st4AnalogToDigitalConvSensors 1 }

    st4AdcSensorHysteresis OBJECT-TYPE
        SYNTAX      Integer32(0..20)
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 8-bit count hysteresis of the analog-to-digital converter
             sensor."
        ::= { st4AdcSensorCommonConfig 1 }

    -- Analog-to-Digital Converter Sensor Configuration Table

    st4AdcSensorConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4AdcSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Analog-to-digital converter sensor configuration table."
        ::= { st4AnalogToDigitalConvSensors 2 }

    st4AdcSensorConfigEntry OBJECT-TYPE
        SYNTAX      St4AdcSensorConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Configuration objects for a particular analog-to-digital
             converter sensor."
        INDEX       { st4UnitIndex, st4AdcSensorIndex }
        ::= { st4AdcSensorConfigTable 1 }

    St4AdcSensorConfigEntry ::= SEQUENCE {
        st4AdcSensorIndex                 Integer32,
        st4AdcSensorID                    DisplayString,
        st4AdcSensorName                  DisplayString
    }

    st4AdcSensorIndex OBJECT-TYPE
        SYNTAX      Integer32(0..1)
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Analog-to-digital converter sensor index."
        ::= { st4AdcSensorConfigEntry 1 }

    st4AdcSensorID OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(2))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The internal ID of the analog-to-digital converter sensor.
             Format=AN."
        ::= { st4AdcSensorConfigEntry 2 }

    st4AdcSensorName OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..32))
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The name of the analog-to-digital converter sensor."
        ::= { st4AdcSensorConfigEntry 3 }

    -- Analog-to-Digital Converter Sensor Monitor Table

    st4AdcSensorMonitorTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4AdcSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Analog-to-digital converter sensor monitor table."
        ::= { st4AnalogToDigitalConvSensors 3 }

    st4AdcSensorMonitorEntry OBJECT-TYPE
        SYNTAX      St4AdcSensorMonitorEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Objects to monitor for a particular analog-to-digital converter
             sensor."
        INDEX       { st4UnitIndex, st4AdcSensorIndex }
        ::= { st4AdcSensorMonitorTable 1 }

    St4AdcSensorMonitorEntry ::= SEQUENCE {
        st4AdcSensorValue                  Integer32,
        st4AdcSensorStatus                 DeviceStatus
    }

    st4AdcSensorValue OBJECT-TYPE
        SYNTAX      Integer32(-1..255)
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The 8-bit value from the analog-to-digital converter sensor."
        ::= { st4AdcSensorMonitorEntry 1 }

    st4AdcSensorStatus OBJECT-TYPE
        SYNTAX      DeviceStatus
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The status of the analog-to-digital converter sensor."
        ::= { st4AdcSensorMonitorEntry 2 }

    -- Analog-to-Digital Converter Sensor Event Configuration Table

    st4AdcSensorEventConfigTable OBJECT-TYPE
        SYNTAX      SEQUENCE OF St4AdcSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Analog-to-digital converter sensor event configuration table."
        ::= { st4AnalogToDigitalConvSensors 4 }

    st4AdcSensorEventConfigEntry OBJECT-TYPE
        SYNTAX      St4AdcSensorEventConfigEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Event configuration objects for a particular 
             analog-to-digital converter sensor."
        INDEX       { st4UnitIndex, st4AdcSensorIndex }
        ::= { st4AdcSensorEventConfigTable 1 }

    St4AdcSensorEventConfigEntry ::= SEQUENCE {
        st4AdcSensorNotifications              EventNotificationMethods,
        st4AdcSensorLowAlarm                   Integer32,
        st4AdcSensorLowWarning                 Integer32,
        st4AdcSensorHighWarning                Integer32,
        st4AdcSensorHighAlarm                  Integer32
    }

    st4AdcSensorNotifications OBJECT-TYPE
        SYNTAX      EventNotificationMethods
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The notification methods enabled for analog-to-digital converter
             sensor events."
        ::= { st4AdcSensorEventConfigEntry 1 }

    st4AdcSensorLowAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..255)
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 8-bit value for the low alarm threshold of the
             analog-to-digital converter sensor."
        ::= { st4AdcSensorEventConfigEntry 2 }

    st4AdcSensorLowWarning OBJECT-TYPE
        SYNTAX      Integer32(0..255)
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 8-bit value for the low warning threshold of the
             analog-to-digital converter sensor."
        ::= { st4AdcSensorEventConfigEntry 3 }

    st4AdcSensorHighWarning OBJECT-TYPE
        SYNTAX      Integer32(0..255)
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 8-bit value for the high warning threshold of the
             analog-to-digital converter sensor."
        ::= { st4AdcSensorEventConfigEntry 4 }

    st4AdcSensorHighAlarm OBJECT-TYPE
        SYNTAX      Integer32(0..255)
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 8-bit value for the high alarm threshold of the
             analog-to-digital converter sensor."
        ::= { st4AdcSensorEventConfigEntry 5 }

    -- Event Information

    st4EventInformation OBJECT IDENTIFIER ::= { st4Objects 99 }

    st4EventStatusText OBJECT-TYPE
        SYNTAX      DisplayString(SIZE(0..20))
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The text representation of the enumerated integer value of
             the most-relevant status or state object included in a trap.
             The value of this object is set only when sent with a trap.
             A read of this object will return a NULL string."
        ::= { st4EventInformation 1 }

    st4EventStatusCondition OBJECT-TYPE
        SYNTAX      INTEGER {
                        nonError(0),
                        error(1)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The condition of the enumerated integer value of the status
             object included in a trap.  The value of this object is set
             only when sent with a trap.  A read of this object will
             return zero."
        ::= { st4EventInformation 2 }

--  Notification Definitions

    st4Notifications OBJECT IDENTIFIER ::= { sentry4 100 }

    -- Events

    st4Events OBJECT IDENTIFIER ::= { st4Notifications 0 }
    -- The 0 is for V1 compatibility

    st4UnitStatusEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4UnitID,
            st4UnitName,
            st4UnitStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Unit status event."
        --#TYPE "Sentry: Unit Status Event."
        --#SUMMARY "Status of Unit '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 4 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 1 }

    st4InputCordStatusEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4InputCordID,
            st4InputCordName,
            st4InputCordState,
            st4InputCordStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Input cord status event."
        --#TYPE "Sentry: Input Cord Status Event."
        --#SUMMARY "Status of Input Cord '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 2 }

    st4InputCordActivePowerEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4InputCordID,
            st4InputCordName,
            st4InputCordActivePower,
            st4InputCordActivePowerStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Input cord active power event."
        --#TYPE "Sentry: Input Cord Active Power Event."
        --#SUMMARY "Active Power Status of Input Cord '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 3 }

    st4InputCordApparentPowerEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4InputCordID,
            st4InputCordName,
            st4InputCordApparentPower,
            st4InputCordApparentPowerStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Input cord apparent power event."
        --#TYPE "Sentry: Input Cord Apparent Power Event."
        --#SUMMARY "Apparent Power Status of Input Cord '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 4 }

    st4InputCordPowerFactorEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4InputCordID,
            st4InputCordName,
            st4InputCordPowerFactor,
            st4InputCordPowerFactorStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Input cord power factor event."
        --#TYPE "Sentry: Input Cord Power Factor Event."
        --#SUMMARY "Power Factor Status of Input Cord '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 5 }

    st4InputCordOutOfBalanceEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4InputCordID,
            st4InputCordName,
            st4InputCordOutOfBalance,
            st4InputCordOutOfBalanceStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Input cord out-of-balance event."
        --#TYPE "Sentry: Input Cord Out-of-Balance Event."
        --#SUMMARY "Out-of-Balance Status of Input Cord '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 6 }

    st4LineStatusEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4LineID,
            st4LineLabel,
            st4LineState,
            st4LineStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Line status event."
        --#TYPE "Sentry: Line Status Event."
        --#SUMMARY "Status of Line '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 7 }

    st4LineCurrentEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4LineID,
            st4LineLabel,
            st4LineCurrent,
            st4LineCurrentStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Line current event."
        --#TYPE "Sentry: Line Current Event."
        --#SUMMARY "Current Status of Line '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 8 }

    st4PhaseStatusEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4PhaseID,
            st4PhaseLabel,
            st4PhaseState,
            st4PhaseStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Phase status event."
        --#TYPE "Sentry: Phase Status Event."
        --#SUMMARY "Status of Phase '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 9 }

    st4PhaseVoltageEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4PhaseID,
            st4PhaseLabel,
            st4PhaseVoltage,
            st4PhaseVoltageStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Phase voltage event."
        --#TYPE "Sentry: Phase Voltage Event."
        --#SUMMARY "Voltage Status of Phase '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 10 }

    st4PhasePowerFactorEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4PhaseID,
            st4PhaseLabel,
            st4PhasePowerFactor,
            st4PhasePowerFactorStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Phase voltage event."
        --#TYPE "Sentry: Phase Power Factor Event."
        --#SUMMARY "Power Factor Status of Phase '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 11 }

    st4OcpStatusEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4OcpID,
            st4OcpLabel,
            st4OcpStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Over-current protector status event."
        --#TYPE "Sentry: Over-current Protector Status Event."
        --#SUMMARY "Status of Over-current Protector '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 4 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 12 }

    st4BranchStatusEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4BranchID,
            st4BranchLabel,
            st4BranchState,
            st4BranchStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Branch status event."
        --#TYPE "Sentry: Branch Status Event."
        --#SUMMARY "Status of Branch '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 13 }

    st4BranchCurrentEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4BranchID,
            st4BranchLabel,
            st4BranchCurrent,
            st4BranchCurrentStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Branch current event."
        --#TYPE "Sentry: Branch Current Event."
        --#SUMMARY "Current Status of Branch '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 14 }

    st4OutletStatusEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4OutletID,
            st4OutletName,
            st4OutletState,
            st4OutletStatus,
            st4OutletControlState,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Outlet status event."
        --#TYPE "Sentry: Outlet Status Event."
        --#SUMMARY "Status of Outlet '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 6 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 15 }

    st4OutletStateChangeEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4OutletID,
            st4OutletName,
            st4OutletState,
            st4OutletStatus,
            st4OutletControlState,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Outlet state change event."
        --#TYPE "Sentry: Outlet State Change Event."
        --#SUMMARY "Outlet '%s' (%s) state has changed to '%s'."
        --#ARGUMENTS { 2, 1, 6 }
        --#SEVERITY INFORMATIONAL
        --#GENERIC 6
        --#CATEGORY "Information Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 16 }

    st4OutletCurrentEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4OutletID,
            st4OutletName,
            st4OutletCurrent,
            st4OutletCurrentStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Outlet current event."
        --#TYPE "Sentry: Outlet Current Event."
        --#SUMMARY "Current Status of Outlet '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 17 }

    st4OutletActivePowerEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4OutletID,
            st4OutletName,
            st4OutletActivePower,
            st4OutletActivePowerStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Outlet active power event."
        --#TYPE "Sentry: Outlet Active Power Event."
        --#SUMMARY "Active Power Status of Outlet '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 18 }

    st4OutletPowerFactorEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4OutletID,
            st4OutletName,
            st4OutletPowerFactor,
            st4OutletPowerFactorStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Outlet power factor event."
        --#TYPE "Sentry: Outlet Power Factor Event."
        --#SUMMARY "Power Factor Status of Outlet '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 19 }

    st4TempSensorEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4TempSensorID,
            st4TempSensorName,
            st4TempSensorValue,
            st4TempSensorStatus,
            st4TempSensorScale,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Temperature sensor event."
        --#TYPE "Sentry: Temperature Sensor Event."
        --#SUMMARY "Status of Temperature Sensor '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 6 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 20 }

    st4HumidSensorEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4HumidSensorID,
            st4HumidSensorName,
            st4HumidSensorValue,
            st4HumidSensorStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Humidity sensor event."
        --#TYPE "Sentry: Humidity Sensor Event."
        --#SUMMARY "Status of Humidity Sensor '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 21 }

    st4WaterSensorStatusEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4WaterSensorID,
            st4WaterSensorName,
            st4WaterSensorStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Water sensor status event."
        --#TYPE "Sentry: Water Sensor Status Event."
        --#SUMMARY "Status of Water Sensor '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 4 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 22 }

    st4CcSensorStatusEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4CcSensorID,
            st4CcSensorName,
            st4CcSensorStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Contact closure sensor status event."
        --#TYPE "Sentry: Contact Closure Sensor Status Event."
        --#SUMMARY "Status of Contact Closure Sensor '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 4 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 23 }

    st4AdcSensorEvent NOTIFICATION-TYPE
        OBJECTS {
            st4SystemLocation,
            st4AdcSensorID,
            st4AdcSensorName,
            st4AdcSensorValue,
            st4AdcSensorStatus,
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Analog-to-digital converter sensor event."
        --#TYPE "Sentry: Analog-to-Digital Converter Sensor Event."
        --#SUMMARY "Status of Analog-to-Digital Converter Sensor '%s' (%s) is '%s'."
        --#ARGUMENTS { 2, 1, 5 }
        --#SEVERITY CRITICAL
        --#GENERIC 6
        --#CATEGORY "Error Events"
        --#SOURCE_ID "A"
        --#TIMEINDEX 255
        --#HELP ""
        --#HELPTAG 0
        --#STATE UNKNOWN
        ::= { st4Events 24 }

--  Conformance Definitions

    st4Conformance OBJECT IDENTIFIER ::= { sentry4 200 }

    -- Object/Notification Groups

    st4Groups OBJECT IDENTIFIER ::= { st4Conformance 1 }

    st4SystemObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4SystemProductName,
            st4SystemLocation,
            st4SystemFirmwareVersion,
            st4SystemFirmwareBuildInfo,
            st4SystemNICSerialNumber,
            st4SystemNICHardwareInfo,
            st4SystemProductSeries,
            st4SystemFeatures,
            st4SystemFeatureKey,
            st4SystemConfigModifiedCount,
            st4SystemUnitCount
        }
        STATUS      current
        DESCRIPTION
            "System objects group."
        ::= { st4Groups 1 }

    st4UnitObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4UnitID,
            st4UnitName,
            st4UnitProductSN,
            st4UnitModel,
            st4UnitAssetTag,
            st4UnitType,
            st4UnitCapabilities,
            st4UnitProductMfrDate,
            st4UnitDisplayOrientation,
            st4UnitOutletSequenceOrder,
            st4UnitInputCordCount,
            st4UnitTempSensorCount,
            st4UnitHumidSensorCount,
            st4UnitWaterSensorCount,
            st4UnitCcSensorCount,
            st4UnitAdcSensorCount,
            st4UnitStatus,
            st4UnitNotifications
        }
        STATUS      current
        DESCRIPTION
            "Unit objects group."
        ::= { st4Groups 2 }

    st4InputCordObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4InputCordActivePowerHysteresis,
            st4InputCordApparentPowerHysteresis,
            st4InputCordPowerFactorHysteresis,
            st4InputCordOutOfBalanceHysteresis,
            st4InputCordID,
            st4InputCordName,
            st4InputCordInletType,
            st4InputCordNominalVoltage,
            st4InputCordNominalVoltageMin,
            st4InputCordNominalVoltageMax,
            st4InputCordCurrentCapacity,
            st4InputCordCurrentCapacityMax,
            st4InputCordPowerCapacity,
            st4InputCordNominalPowerFactor,
            st4InputCordLineCount,
            st4InputCordPhaseCount,
            st4InputCordOcpCount,
            st4InputCordBranchCount,
            st4InputCordOutletCount,
            st4InputCordState,
            st4InputCordStatus,
            st4InputCordActivePower,
            st4InputCordActivePowerStatus,
            st4InputCordApparentPower,
            st4InputCordApparentPowerStatus,
            st4InputCordPowerUtilized,
            st4InputCordPowerFactor,
            st4InputCordPowerFactorStatus,
            st4InputCordEnergy,
            st4InputCordFrequency,
            st4InputCordOutOfBalance,
            st4InputCordOutOfBalanceStatus,
            st4InputCordNotifications,
            st4InputCordActivePowerLowAlarm,
            st4InputCordActivePowerLowWarning,
            st4InputCordActivePowerHighWarning,
            st4InputCordActivePowerHighAlarm,
            st4InputCordApparentPowerLowAlarm,
            st4InputCordApparentPowerLowWarning,
            st4InputCordApparentPowerHighWarning,
            st4InputCordApparentPowerHighAlarm,
            st4InputCordPowerFactorLowAlarm,
            st4InputCordPowerFactorLowWarning,
            st4InputCordOutOfBalanceHighWarning,
            st4InputCordOutOfBalanceHighAlarm
        }
        STATUS      current
        DESCRIPTION
            "Input cord objects group."
        ::= { st4Groups 3 }

    st4LineObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4LineCurrentHysteresis,
            st4LineID,
            st4LineLabel,
            st4LineCurrentCapacity,
            st4LineState,
            st4LineStatus,
            st4LineCurrent,
            st4LineCurrentStatus,
            st4LineCurrentUtilized,
            st4LineNotifications,
            st4LineCurrentLowAlarm,
            st4LineCurrentLowWarning,
            st4LineCurrentHighWarning,
            st4LineCurrentHighAlarm
        }
        STATUS      current
        DESCRIPTION
            "Line objects group."
        ::= { st4Groups 4 }

    st4PhaseObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4PhaseVoltageHysteresis,
            st4PhasePowerFactorHysteresis,
            st4PhaseID,
            st4PhaseLabel,
            st4PhaseNominalVoltage,
            st4PhaseBranchCount,
            st4PhaseOutletCount,
            st4PhaseState,
            st4PhaseStatus,
            st4PhaseVoltage,
            st4PhaseVoltageStatus,
            st4PhaseVoltageDeviation,
            st4PhaseCurrent,
            st4PhaseCurrentCrestFactor,
            st4PhaseActivePower,
            st4PhaseApparentPower,
            st4PhasePowerFactor,
            st4PhasePowerFactorStatus,
            st4PhaseReactance,
            st4PhaseEnergy,
            st4PhaseNotifications,
            st4PhaseVoltageLowAlarm,
            st4PhaseVoltageLowWarning,
            st4PhaseVoltageHighWarning,
            st4PhaseVoltageHighAlarm,
            st4PhasePowerFactorLowAlarm,
            st4PhasePowerFactorLowWarning
        }
        STATUS      current
        DESCRIPTION
            "Phase objects group."
        ::= { st4Groups 5 }

    st4OcpObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4OcpID,
            st4OcpLabel,
            st4OcpType,
            st4OcpCurrentCapacity,
            st4OcpCurrentCapacityMax,
            st4OcpBranchCount,
            st4OcpOutletCount,
            st4OcpStatus,
            st4OcpNotifications
        }
        STATUS      current
        DESCRIPTION
            "Over-current protector objects group."
        ::= { st4Groups 6 }

    st4BranchObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4BranchCurrentHysteresis,
            st4BranchID,
            st4BranchLabel,
            st4BranchCurrentCapacity,
            st4BranchPhaseID,
            st4BranchOcpID,
            st4BranchOutletCount,
            st4BranchState,
            st4BranchStatus,
            st4BranchCurrent,
            st4BranchCurrentStatus,
            st4BranchCurrentUtilized,
            st4BranchNotifications,
            st4BranchCurrentLowAlarm,
            st4BranchCurrentLowWarning,
            st4BranchCurrentHighWarning,
            st4BranchCurrentHighAlarm
        }
        STATUS      current
        DESCRIPTION
            "Branch objects group."
        ::= { st4Groups 7 }

    st4OutletObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4OutletCurrentHysteresis,
            st4OutletActivePowerHysteresis,
            st4OutletPowerFactorHysteresis,
            st4OutletSequenceInterval,
            st4OutletRebootDelay,
            st4OutletStateChangeLogging,
            st4OutletID,
            st4OutletName,
            st4OutletCapabilities,
            st4OutletSocketType,
            st4OutletCurrentCapacity,
            st4OutletPowerCapacity,
            st4OutletWakeupState,
            st4OutletPostOnDelay,
            st4OutletPhaseID,
            st4OutletOcpID,
            st4OutletBranchID,
            st4OutletState,
            st4OutletStatus,
            st4OutletCurrent,
            st4OutletCurrentStatus,
            st4OutletCurrentUtilized,
            st4OutletVoltage,
            st4OutletActivePower,
            st4OutletActivePowerStatus,
            st4OutletApparentPower,
            st4OutletPowerFactor,
            st4OutletPowerFactorStatus,
            st4OutletCurrentCrestFactor,
            st4OutletReactance,
            st4OutletEnergy,
            st4OutletNotifications,
            st4OutletCurrentLowAlarm,
            st4OutletCurrentLowWarning,
            st4OutletCurrentHighWarning,
            st4OutletCurrentHighAlarm,
            st4OutletActivePowerLowAlarm,
            st4OutletActivePowerLowWarning,
            st4OutletActivePowerHighWarning,
            st4OutletActivePowerHighAlarm,
            st4OutletPowerFactorLowAlarm,
            st4OutletPowerFactorLowWarning,
            st4OutletControlState,
            st4OutletControlAction,
            st4OutletQueueControl
        }
        STATUS      current
        DESCRIPTION
            "Outlet objects group."
        ::= { st4Groups 8 }

    st4TempSensorObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4TempSensorHysteresis,
            st4TempSensorScale,
            st4TempSensorID,
            st4TempSensorName,
            st4TempSensorValueMin,
            st4TempSensorValueMax,
            st4TempSensorValue,
            st4TempSensorStatus,
            st4TempSensorNotifications,
            st4TempSensorLowAlarm,
            st4TempSensorLowWarning,
            st4TempSensorHighWarning,
            st4TempSensorHighAlarm
        }
        STATUS      current
        DESCRIPTION
            "Temperature sensor objects group."
        ::= { st4Groups 9 }

    st4HumidSensorObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4HumidSensorHysteresis,
            st4HumidSensorID,
            st4HumidSensorName,
            st4HumidSensorValue,
            st4HumidSensorStatus,
            st4HumidSensorNotifications,
            st4HumidSensorLowAlarm,
            st4HumidSensorLowWarning,
            st4HumidSensorHighWarning,
            st4HumidSensorHighAlarm
        }
        STATUS      current
        DESCRIPTION
            "Humidity sensor objects group."
        ::= { st4Groups 10 }

    st4WaterSensorObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4WaterSensorID,
            st4WaterSensorName,
            st4WaterSensorStatus,
            st4WaterSensorNotifications
        }
        STATUS      current
        DESCRIPTION
            "Water sensor objects group."
        ::= { st4Groups 11 }

    st4CcSensorObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4CcSensorID,
            st4CcSensorName,
            st4CcSensorStatus,
            st4CcSensorNotifications
        }
        STATUS      current
        DESCRIPTION
            "Contact closure sensor objects group."
        ::= { st4Groups 12 }

    st4AdcSensorObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4AdcSensorHysteresis,
            st4AdcSensorID,
            st4AdcSensorName,
            st4AdcSensorValue,
            st4AdcSensorStatus,
            st4AdcSensorNotifications,
            st4AdcSensorLowAlarm,
            st4AdcSensorLowWarning,
            st4AdcSensorHighWarning,
            st4AdcSensorHighAlarm
        }
        STATUS      current
        DESCRIPTION
            "Analog-to-digital converter sensor objects group."
        ::= { st4Groups 13 }

    st4EventInfoObjectsGroup OBJECT-GROUP
        OBJECTS {
            st4EventStatusText,
            st4EventStatusCondition
        }
        STATUS      current
        DESCRIPTION
            "Event information objects group."
        ::= { st4Groups 99 }

    st4EventNotificationsGroup NOTIFICATION-GROUP
        NOTIFICATIONS {
            st4UnitStatusEvent,
            st4InputCordStatusEvent,
            st4InputCordActivePowerEvent,
            st4InputCordApparentPowerEvent,
            st4InputCordPowerFactorEvent,
            st4InputCordOutOfBalanceEvent,
            st4LineStatusEvent,
            st4LineCurrentEvent,
            st4PhaseStatusEvent,
            st4PhaseVoltageEvent,
            st4PhasePowerFactorEvent,
            st4OcpStatusEvent,
            st4BranchStatusEvent,
            st4BranchCurrentEvent,
            st4OutletStatusEvent,
            st4OutletStateChangeEvent,
            st4OutletCurrentEvent,
            st4OutletActivePowerEvent,
            st4OutletPowerFactorEvent,
            st4TempSensorEvent,
            st4HumidSensorEvent,
            st4WaterSensorStatusEvent,
            st4CcSensorStatusEvent,
            st4AdcSensorEvent
        }
        STATUS      current
        DESCRIPTION
            "Event notifications group."
        ::= { st4Groups 100 }

    -- Compliance Statements

    st4Compliances OBJECT IDENTIFIER ::= { st4Conformance 2 }

    st4ModuleCompliances MODULE-COMPLIANCE
        STATUS current
        DESCRIPTION
            "The requirements for conformance to the Sentry4-MIB."
        MODULE
        GROUP st4SystemObjectsGroup
        DESCRIPTION
            "System objects group."
        GROUP st4UnitObjectsGroup
        DESCRIPTION
            "Unit objects group."
        GROUP st4InputCordObjectsGroup
        DESCRIPTION
            "Input cord objects group."
        GROUP st4LineObjectsGroup
        DESCRIPTION
            "Line objects group."
        GROUP st4PhaseObjectsGroup
        DESCRIPTION
            "Phase objects group."
        GROUP st4OcpObjectsGroup
        DESCRIPTION
            "Over-current protector objects group."
        GROUP st4BranchObjectsGroup
        DESCRIPTION
            "Branch objects group."
        GROUP st4OutletObjectsGroup
        DESCRIPTION
            "Outlet objects group."
        GROUP st4TempSensorObjectsGroup
        DESCRIPTION
            "Temperature sensor objects group."
        GROUP st4HumidSensorObjectsGroup
        DESCRIPTION
            "Humidity sensor objects group."
        GROUP st4WaterSensorObjectsGroup
        DESCRIPTION
            "Water sensor objects group."
        GROUP st4CcSensorObjectsGroup
        DESCRIPTION
            "Contact closure sensor objects group."
        GROUP st4AdcSensorObjectsGroup
        DESCRIPTION
            "Analog-to-digital converter sensor objects group."
        GROUP st4EventInfoObjectsGroup
        DESCRIPTION
            "Event information objects group."
        GROUP st4EventNotificationsGroup
        DESCRIPTION
            "Event notifications group."
        ::= { st4Compliances 1 }

END