XUPS-MIB DEFINITIONS ::= BEGIN

IMPORTS
    TimeTicks, Gauge32, Counter32, Integer32 
        FROM SNMPv2-SMI
    DisplayString
        FROM SNMPv2-TC
    MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE
        FROM SNMPv2-SMI
    MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP 
        FROM SNMPv2-CONF
    sysName
        FROM RFC1213-MIB
    eaton, xupsEnvironment
        FROM EATON-OIDS
    -- Need to import these EMP objects to support PowerMIB-style traps for EMP
    xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr,
    xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit, xupsEnvRemoteTempUpperLimit,
    xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit, 
    xupsEnvRemoteHumidityUpperLimit
        FROM EATON-EMP-MIB;

xupsMIB MODULE-IDENTITY
    LAST-UPDATED "201909270000Z"
    ORGANIZATION "Eaton Corporation"
    CONTACT-INFO
        "Eaton Power Quality Technical Support (PQTS) group
            www.eaton.com/powerxpert 
            Technical Resource Center phone numbers 
            United States:  1.800.843.9433 or 919.870.3028
            Canada:  1.800.461.9166 ext. 260
            All other countries:  Call your local service representative." 
    DESCRIPTION
            "Defines Eaton's proprietary PowerMIB for UPS and
             related device data.

            Copyright (C) Exide Electronics 1992-98
            Copyright (C) Powerware Corporation 1999-2004
            Copyright (C) Eaton Corporation (2005-)."

    REVISION "201909270000Z"
    DESCRIPTION 
        "xupsOutputSource data can monitor the ESS mode."

    REVISION "201909120000Z"
    DESCRIPTION 
        "Provide new data that reflects some battery alarm : xupsBatteryFailure,
         xupsBatteryNotPresent, xupsBatteryAged, xupsBatteryLowCapacity."

    REVISION "201909100000Z"
    DESCRIPTION 
        "Change the data xupsBatteryLastReplacedDate to read-only because the card
         sets it automatically when the battery replacement is detected."

    REVISION "201904120000Z"
    DESCRIPTION 
        "Provide the status of the main AC Input in xupsInputStatus.
         Provide the status of the AC Output in xupsOutputStatus and a new trap
         and alarm 'load not protected' in xupsOutputNotProtected." 

    REVISION "201903050000Z"
    DESCRIPTION 
        "Provide more UPS identification data as xupsIdentPartNumber and xupsIdentSerialNumber.
         Provide a collection xupsAgent that contains identification data of the card :
         xupsAgentManufacturer, xupsAgentModel, xupsAgentSoftwareVersion, xupsAgentPartNumber,
         xupsAgentSerialNumber"

    REVISION "201902190000Z"
    DESCRIPTION 
        "To ensure consistency whith the measures done on the UPS, the data following are renamed :
         xupsInputAverageCurrent to xupsInputTotalCurrent,
         xupsOutputAverageCurrent to xupsOutputTotalCurrent,
         xupsBypassAverageCurrent to xupsBypassTotalCurrent."

    REVISION "201809120000Z"
    DESCRIPTION 
        "Add new data xupsInputId, xupsInputName, xupsInputCurrentHighPrecision in the table xupsInputTable.
         Add new sub collection xupsInputTotal with xupsInputAverageVoltage, xupsInputAverageCurrent,
         xupsInputTotalWatts, xupsInputTotalVA, xupsInputAveragePowerFactor inside.
         Add new data xupsOutputId, xupsOutputName, xupsOutputCurrentHighPrecision,
         xupsOutputPercentLoad, xupsOutputVA in the table xupsOutputTable.
         Add new sub collection xupsOutputTotal with xupsOutputAverageVoltage, xupsOutputAverageCurrent,
         xupsOutputTotalWatts, xupsOutputTotalVA, xupsOutputAveragePowerFactor inside.
         Add new data xupsBypassId, xupsBypassName, xupsBypassCurrentHighPrecision,
         xupsBypassWatts in the table xupsBypassTable.
         Add new sub collection xupsBypassTotal with xupsBypassTotalAverageVoltage, xupsBypassAverageCurrent,
         xupsBypassTotalWatts, xupsBypassTotalVA, xupsBypassTotalAverageFactor inside."

    REVISION "201804230000Z"
    DESCRIPTION 
        "Add new data xupsTestTrap, xupstdTestTrap that will allow to initiate a 
         test trap sent out from the agent to the trap receivers."

    REVISION "201211261513Z"
    DESCRIPTION 
        "Add the identifier of measures xupsInputId, xupsOutputId and xupsBypassId,
         respectively in the table xupsInputTable, xupsOutputTable and xupsBypassTable."

    REVISION "201204030000Z"
    DESCRIPTION 
        "Add new data xupsOutputHourlyPowerUsage, xupsOutputCumulativePowerUsage,
         and xupsOutputCumulativePowerUsageTimer into the collection xupsOutput.
         Add new data xupsRecepHourlyPowerUsage, xupsRecepCumulativePowerUsage,
         and xupsRecepCumulativePowerUsageTimer into the collection xupsRecepTable."

    REVISION "201102250000Z"
    DESCRIPTION 
        "Add new data xupsSwitchable"

    REVISION        "200810020000Z"
    DESCRIPTION
            "Added new values of batteryDisconnected(6), batteryUnderTest(7), 
             and checkBattery(8)  to xupsBatteryAbmStatus."
 
    REVISION        "200705030000Z"
    DESCRIPTION
            "Added new value of pxg(5) to xupsSendTrapType
             for Power Xpert Gateway implementations."

    REVISION        "200703130000Z"
    DESCRIPTION
            "Initial SNMPv2-SMI-compliant Version of PowerMIB.
             Incorporates all revisions of the original xups
             MIB file through Version 3.13 21-May-04."

    ::= { eaton 1 }

-- xupsMIB { iso org(3) dod(6) internet(1) private(4)
--       enterprises(1) eaton(534) xupsMIB(1) }


xupsIdent        OBJECT IDENTIFIER       ::= { xupsMIB 1 }
xupsBattery      OBJECT IDENTIFIER       ::= { xupsMIB 2 }
xupsInput        OBJECT IDENTIFIER       ::= { xupsMIB 3 }
xupsOutput       OBJECT IDENTIFIER       ::= { xupsMIB 4 }
xupsBypass       OBJECT IDENTIFIER       ::= { xupsMIB 5 }
-- xupsEnvironment  OBJECT IDENTIFIER    ::= { xupsMIB 6 } - defined in EATON-OIDS
xupsAlarm        OBJECT IDENTIFIER       ::= { xupsMIB 7 }
xupsTest         OBJECT IDENTIFIER       ::= { xupsMIB 8 }
xupsControl      OBJECT IDENTIFIER       ::= { xupsMIB 9 }
xupsConfig       OBJECT IDENTIFIER       ::= { xupsMIB 10 }
xupsTrapControl  OBJECT IDENTIFIER       ::= { xupsMIB 11 }
xupsRecep        OBJECT IDENTIFIER       ::= { xupsMIB 12 }
xupsTopology     OBJECT IDENTIFIER       ::= { xupsMIB 13 }
xupsAgent        OBJECT IDENTIFIER       ::= { xupsMIB 14 }

xupsInputTotal   OBJECT IDENTIFIER       ::= { xupsInput 8 }
xupsOutputTotal   OBJECT IDENTIFIER       ::= { xupsOutput 9 }
xupsBypassTotal   OBJECT IDENTIFIER       ::= { xupsBypass 4 }

--
-- xupsIdent group:
--
xupsIdentManufacturer OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..31))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The UPS Manufacturer Name (e.g. Eaton Corporation)."
    ::= { xupsIdent 1}

xupsIdentModel OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..63))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The UPS Model (e.g. Powerware Plus Model 18)."
    ::= {xupsIdent 2}

xupsIdentSoftwareVersion OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..63))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The firmware revision level(s) of the UPS microcontroller(s)."
    ::= {xupsIdent 3}

xupsIdentOemCode OBJECT-TYPE
    SYNTAX     Integer32 (0..255)  
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "A binary code indicating who the UPS was manufactured or labeled for.  
         0 or 255 indicates Eaton itself."
    ::= {xupsIdent 4}

xupsIdentPartNumber  OBJECT-TYPE
    SYNTAX     OCTET STRING (SIZE(1..31))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION 
        "The catalog part number of the UPS device."
    ::= { xupsIdent 5 }

xupsIdentSerialNumber  OBJECT-TYPE
    SYNTAX     OCTET STRING (SIZE(1..31))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION 
        "The serial number of the UPS device."
    ::= { xupsIdent 6 }


--
-- xupsBattery group:
--
xupsBatTimeRemaining OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "seconds"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "Battery run time in seconds before UPS turns off due
         to low battery."
    ::= { xupsBattery 1}

xupsBatVoltage OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "Volts DC"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "Battery voltage as reported by the UPS meters."
    ::= {xupsBattery 2}

xupsBatCurrent OBJECT-TYPE
    SYNTAX     Integer32 (-2147483648..2147483647)   
    UNITS      "Amps DC"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "Battery Current as reported by the UPS metering.
         Current is positive when discharging, negative
         when recharging the battery."
    ::= {xupsBattery 3}

xupsBatCapacity OBJECT-TYPE
    SYNTAX     Integer32 (0..100)
    UNITS      "percent"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "Battery percent charge."
    ::= { xupsBattery 4}

xupsBatteryAbmStatus OBJECT-TYPE
    SYNTAX  INTEGER {
    batteryCharging(1),
    batteryDischarging(2),
    batteryFloating(3),
    batteryResting(4),
    unknown(5),
    batteryDisconnected(6),
    batteryUnderTest(7),
    checkBattery(8)
    }
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
    "Gives the status of the Advanced Battery Management and Battery state;
     batteryFloating(3) status means that the charger is temporarily 
     charging the battery to its float voltage; batteryResting(4) is the 
     state when the battery is fully charged and none of the other actions 
     (charging/discharging/floating) is being done.
     checkBattery(8) indicates that the Battery state is uncertain
     following a poor battery test result."
    ::= { xupsBattery 5}

xupsBatteryLastReplacedDate OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..16))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
    "The date when the Batteries in this UPS were last replaced. Free text format,
     so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc)."
    ::= { xupsBattery 6}

xupsBatteryFailure OBJECT-TYPE
    SYNTAX INTEGER {
        yes(1),
        no(2)
    }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
    "Indicates if a battery fault detected or battery tests failed."
    ::= { xupsBattery 7}

xupsBatteryNotPresent OBJECT-TYPE
    SYNTAX INTEGER {
        yes(1),
        no(2)
    }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
    "Indicates if the UPS has no battery either internal or external."
    ::= { xupsBattery 8}

xupsBatteryAged OBJECT-TYPE
    SYNTAX INTEGER {
        yes(1),
        no(2)
    }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
    "Indicates if the battery is over aged."
    ::= { xupsBattery 9}

xupsBatteryLowCapacity OBJECT-TYPE
    SYNTAX INTEGER {
        yes(1),
        no(2)
    }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
    "Indicates if the battery capacity is below the threshold set in the UPS."
    ::= { xupsBattery 10}


--
-- xupsInput group:
--
xupsInputFrequency OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "0.1 Hertz"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The utility line frequency in tenths of Hz."
    ::= {xupsInput 1}

xupsInputLineBads OBJECT-TYPE
    SYNTAX Counter32
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The number of times the Input was out of tolerance
         in voltage or frequency."
    ::= {xupsInput 2}

xupsInputNumPhases OBJECT-TYPE
    SYNTAX     Integer32 (0..6)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
           "The number of input phases (normally 1 to 3)."
    ::= {xupsInput 3}

xupsInputTable OBJECT-TYPE
    SYNTAX SEQUENCE OF XupsInputEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION 
       "A list of input table entries.  The number of entries
        is given by the value of xupsInputNumPhases."
    ::= {xupsInput 4}

xupsInputEntry OBJECT-TYPE
    SYNTAX XupsInputEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION 
        "The input table entry containing the current,
         voltage, etc. readings for one phase."
    INDEX { xupsInputPhase }
    ::= { xupsInputTable 1 }

XupsInputEntry ::= SEQUENCE {
    xupsInputPhase   Integer32,
    xupsInputVoltage Integer32,
    xupsInputCurrent Integer32,
    xupsInputWatts   Integer32,
    xupsInputId      INTEGER,
    xupsInputName    OCTET STRING,
    xupsInputCurrentHighPrecision Integer32
    }

xupsInputPhase OBJECT-TYPE
    SYNTAX     Integer32  (0..6)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The number of the phase.  Serves as index for input table."
    ::= {xupsInputEntry 1}

xupsInputVoltage OBJECT-TYPE
    SYNTAX     Integer32  (0..2147483647)  
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured input voltage from the UPS meters in volts."
    ::= {xupsInputEntry 2}

xupsInputCurrent OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS Amps"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured input current from the UPS meters in amps."
    ::= {xupsInputEntry 3}

xupsInputWatts OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured input real power in watts."
    ::= {xupsInputEntry 4}

xupsInputId  OBJECT-TYPE
	SYNTAX     INTEGER {
		phase1toN (1),
		phase2toN (2),
		phase3toN (3),
		phase1to2 (4),
		phase2to3 (5),
		phase3to1 (6)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"value indicates what measurement is being stored in this table row :
		phase1 to neutral, phase2 to neutral, phase3 to neutral,
		phase1 to phase2, phase2 to phase3, phase3 to phase1."
	::= { xupsInputEntry 5 }

xupsInputName  OBJECT-TYPE
	SYNTAX     OCTET STRING (SIZE(1..31))
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"A descriptive name for the phase, example : L1/A for the phase 1."
	::= { xupsInputEntry 6 }

xupsInputCurrentHighPrecision OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS tenth of Amps"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured input current from the UPS meters in tenth of amps."
    ::= {xupsInputEntry 7}

xupsInputSource OBJECT-TYPE
    SYNTAX     INTEGER {
        other(1),
        none(2),                
        primaryUtility(3),      
        bypassFeed(4),          
        secondaryUtility(5),    
        generator(6),           
        flywheel(7),            
        fuelcell(8)             
        }
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
       "The present external source of input power.  The enumeration
        'none(2)' indicates that there is no external source of 
        power, for example, the UPS is On Battery (an internal source).
		'primaryUtility' indicates the normal case of utility input power.
        The 'bypassFeed' can only be used when the Bypass source is known
        to be a separate utility feed than the primaryUtility(3).
		'secondaryUtility' indicates that a secondary utility feed is supplying
		power (on a dual AC input UPS).
        'generator' indicates that input power is provided by a generator.
		Note that the alternate energy sources of 'flywheel' and 'fuelcell' are 
		not necessarily AC input sources."
    ::= { xupsInput 5 }

-- xupsDualInputStatus and xupsSecondaryInputWatch would only be present
-- for UPSs with a secondary input source.

xupsDualInputStatus OBJECT-TYPE
    SYNTAX     INTEGER {
        bothSourcesBad(1),      
        primarySourceGood(2),   
        secondarySourceGood(3), 
        bothSourcesGood(4)      
        }
    MAX-ACCESS  read-only
    STATUS      current           
    DESCRIPTION
       "The present status of the sources of input power in a dual source UPS.  
        The enumeration primarySourceGood(2) indicates that the primary source
        of power is present and within 'normal' ranges for voltage and
        frequency, but the secondary source is either not present or not in an
        acceptable range.
		'secondarySourceGood' indicates that only the Secondary power feed is 
		available and within its limits.
        The enumeration bothSourcesGood(4) indicates that both sources are present
        and within their respective 'normal' ranges; 
        bothSourcesBad(1) indicates that neither source is present, or, if present, 
        is not within acceptable ranges.
        This object will only be implemented for UPSs with two sources of input
        power, e.g., redundant AC feeds or a separate Bypass or Generator source.
        The secondary source will not be an AC power source in all cases."
    ::= { xupsInput 6 }

xupsSecondaryInputWatch OBJECT-TYPE
    SYNTAX      INTEGER {
        disabled(1),            
        enabled(2)     
        }
    MAX-ACCESS  read-write
    STATUS      current           
    DESCRIPTION
       "This object enables(2) or disables(1) the alarms and traps related to the
        availability and use of the secondary input of a dual-input UPS
        (i.e., OnAlternatePowerSource and AltPowerNotAvailable).
        To avoid nuisance alarms and traps, this object should be set to  
        disabled(1) when the UPS is not wired to a secondary source of power.
        This object will only be implemented for UPSs with two sources of input
        power, i.e., redundant AC feeds or a separate Bypass or Generator source."
    ::= { xupsInput 7 }

--
-- xupsInputTotal group:
--
xupsInputAverageVoltage OBJECT-TYPE
    SYNTAX     Integer32  (0..2147483647)  
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured input voltage from the UPS meters in volts.
         Related to the phase 1 if the UPS is single phase,
         either it is average of all the simple phase voltage."
    ::= {xupsInputTotal 1}

xupsInputTotalCurrent OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS tenth of Amps"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured input current from the UPS meters in tenth of amps.
         Related to the phase 1 if the UPS is single phase,
         either it is average of all the simple phase current."
    ::= {xupsInputTotal 2}

xupsInputTotalWatts OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured input active power in watts.
         Sum of all the simple phase watts."
    ::= {xupsInputTotal 3}

xupsInputTotalVA OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "VA"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured input apparent power in VA.
         Sum of all the simple phase VA."
    ::= {xupsInputTotal 4}

xupsInputAveragePowerFactor  OBJECT-TYPE
    SYNTAX     Integer32  
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION 
      "Indicates the total power factor of the input in hundredths.
       0.92 would be returned as 92."
    ::= { xupsInputTotal 5 }

xupsInputStatus OBJECT-TYPE
    SYNTAX     INTEGER {
        inputBad(1),
        inputGood(2)
        }
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
       "The present status of the primary AC input of the UPS.
        The enumeration inputGood(2) indicates that the primary source
        of power is present and within 'normal' ranges for voltage and
        frequency.
        inputBad(1) indicates that neither source is present, or, if present,
        is not within acceptable ranges."
    ::= { xupsInput 9 }

--
-- xupsOutput group:
--
xupsOutputLoad OBJECT-TYPE
    SYNTAX     Integer32 (0..200)
    UNITS      "percent"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The UPS output load in percent of rated capacity."
    ::= {xupsOutput 1}

xupsOutputFrequency OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "0.1 Hertz"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured UPS output frequency in tenths of Hz."
    ::= {xupsOutput 2}

xupsOutputNumPhases OBJECT-TYPE
    SYNTAX     Integer32  (0..6)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The number of metered output phases."
    ::= {xupsOutput 3}

xupsOutputTable OBJECT-TYPE
    SYNTAX SEQUENCE OF XupsOutputEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
       "A list of output table entries.  The number of entries
        is given by the value of xupsOutputNumPhases."
    ::= {xupsOutput 4}

xupsOutputEntry OBJECT-TYPE
    SYNTAX XupsOutputEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
        "Output Table Entry containing voltage, current, etc."
    INDEX { xupsOutputPhase }
    ::= {xupsOutputTable 1}

XupsOutputEntry ::= SEQUENCE {
        xupsOutputPhase    Integer32,
        xupsOutputVoltage  Integer32,
        xupsOutputCurrent  Integer32,
        xupsOutputWatts    Integer32,
   	    xupsOutputId       INTEGER,
   	    xupsOutputName     OCTET STRING,
        xupsOutputCurrentHighPrecision Integer32,
        xupsOutputPercentLoad Integer32,
        xupsOutputVA Integer32
        }

xupsOutputPhase OBJECT-TYPE
    SYNTAX     Integer32 (0..6)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The number of the phase.  Serves as index for output table."
    ::= {xupsOutputEntry 1}

xupsOutputVoltage OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured output voltage from the UPS metering in volts."
    ::= {xupsOutputEntry 2}

xupsOutputCurrent OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "RMS Amps"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured UPS output current in amps."
    ::= {xupsOutputEntry 3}

xupsOutputWatts OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured real output power in watts."
    ::= {xupsOutputEntry 4}

xupsOutputId  OBJECT-TYPE
	SYNTAX     INTEGER {
		phase1toN (1),
		phase2toN (2),
		phase3toN (3),
		phase1to2 (4),
		phase2to3 (5),
		phase3to1 (6)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"value indicates what measurement is being stored in this table row :
		phase1 to neutral, phase2 to neutral, phase3 to neutral,
		phase1 to phase2, phase2 to phase3, phase3 to phase1. "
	::= { xupsOutputEntry 5 }

xupsOutputName  OBJECT-TYPE
	SYNTAX     OCTET STRING (SIZE(1..31))
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"A descriptive name for the phase."
	::= { xupsOutputEntry 6 }

xupsOutputCurrentHighPrecision OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS tenth of Amps"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured output current from the UPS meters in tenth of amps."
    ::= {xupsOutputEntry 7}

xupsOutputPercentLoad OBJECT-TYPE
    SYNTAX     Integer32  (0..200)
    UNITS      "percent"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The percentage of the UPS power capacity presently
         being used on this output line"
    ::= { xupsOutputEntry 8 }

xupsOutputVA OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "VA"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured apparent output power in VA."
    ::= {xupsOutputEntry 9}

xupsOutputSource OBJECT-TYPE
    SYNTAX  INTEGER {
        other(1),
        none(2),
        normal(3),              
        bypass(4),
        battery(5),
        booster(6),             
        reducer(7),             
        parallelCapacity(8),    
        parallelRedundant(9),   
        highEfficiencyMode(10), 
        maintenanceBypass(11),   
        essMode(12)   
        }
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
       "The present source of output power.  The enumeration
        none(2) indicates that there is no source of output
        power (and therefore no output power), for example,
        the system has opened the output breaker.
		'normal', 'bypass', and 'battery' indicate those common UPS statuses.
		'booster' and 'reducer' indicate boost or buck operation, for 
		line-interactive UPSs only.
		'parallelCapacity' and 'parallelRedundant' indicate a normal parallel
		UPS system, in either Parallel for Capacity or Redundancy configuration.
		'highEfficiencyMode' is normal but enhanced by High Efficiency mode.
		'maintenanceBypass' indicates that the UPS is in Maintenance/Manual 
		Bypass mode.
		'essMode' is normal but enhanced by Energy Saver System.
		'other' covers any other, unusual conditions."
    ::= { xupsOutput  5 }

xupsOutputHourlyPowerUsage  OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "Wh"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Units are Watt-hours.This is the energy consumed during the last hour."
	::= { xupsOutput 6 }

xupsOutputCumulativePowerUsage  OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "Wh"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Units are Watt-hours.This is the energy consumed since the last reset.
         This object is writable so that it can be reset to 0.
         When it is written to 0, the xupsOutputCumulativeWhTimer will be reset to 0 as well."
	::= { xupsOutput 7 }

xupsOutputCumulativePowerUsageTimer  OBJECT-TYPE
    SYNTAX     Counter32
    UNITS      "Seconds"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Time in seconds since the cumulative power usage was last reset."
	::= { xupsOutput 8 }

--
-- xupsOutputTotal group:
--
xupsOutputAverageVoltage OBJECT-TYPE
    SYNTAX     Integer32  (0..2147483647)  
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured output voltage from the UPS meters in volts.
         Related to the phase 1 if the UPS is single phase,
         either it is average of all the simple phase voltage."
    ::= {xupsOutputTotal 1}

xupsOutputTotalCurrent OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS tenth of Amps"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured output current from the UPS meters in tenth of amps.
         Related to the phase 1 if the UPS is single phase,
         either it is average of all the simple phase current."
    ::= {xupsOutputTotal 2}

xupsOutputTotalWatts OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured output active power in watts.
         Sum of all the simple phase watts."
    ::= {xupsOutputTotal 3}

xupsOutputTotalVA OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "VA"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured output apparent power in VA.
         Sum of all the simple phase VA."
    ::= {xupsOutputTotal 4}

xupsOutputAveragePowerFactor  OBJECT-TYPE
    SYNTAX     Integer32  
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION 
      "Indicates the total power factor of the output in hundredths.
       0.92 would be returned as 92."
    ::= { xupsOutputTotal 5 }

xupsOutputStatus OBJECT-TYPE
    SYNTAX     INTEGER {
        outputNotPowered(1),   
        outputNotProtected(2),   
        outputProtected(3)   
        }
    MAX-ACCESS  read-only
    STATUS      current           
    DESCRIPTION
       "The present status of the AC output of the UPS.  
        The enumeration outputNotPowered(1) indicates that the output is not powered.
        outputNotProtected(2) indicates that the output is powered but not protected,
        due to following reasons : On bypass, battery fault, or UPS internal failure
        that makes the ups will be inoperant in case of AC input failure.
        outputProtected(3) indicates that the output is powered and protected."
    ::= { xupsOutput 10 }


--
-- xupsBypass group:
--
xupsBypassFrequency OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "0.1 Hertz"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The bypass frequency in tenths of Hz."
    ::= {xupsBypass 1}

xupsBypassNumPhases OBJECT-TYPE
    SYNTAX     Integer32 (0..6)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The number of lines in the UPS bypass table."
    ::= {xupsBypass 2}

xupsBypassTable OBJECT-TYPE
    SYNTAX SEQUENCE OF XupsBypassEntry
    MAX-ACCESS not-accessible 
    STATUS     current
    DESCRIPTION
       "A list of bypass table entries.  The number of entries
        is given by the value of xupsBypassNumPhases."
    ::= {xupsBypass 3}

xupsBypassEntry OBJECT-TYPE
    SYNTAX XupsBypassEntry
    MAX-ACCESS not-accessible 
    STATUS     current
    DESCRIPTION
        "Bypass Table Entry containing voltage for each phase."
    INDEX { xupsBypassPhase }
    ::= {xupsBypassTable 1}

XupsBypassEntry ::= SEQUENCE {
        xupsBypassPhase    Integer32,
        xupsBypassVoltage  Integer32,
      	xupsBypassId       INTEGER,
      	xupsBypassName     OCTET STRING,
        xupsBypassCurrentHighPrecision Integer32,
        xupsBypassWatts Integer32
        }

xupsBypassPhase OBJECT-TYPE
    SYNTAX     Integer32 (0..6)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The Bypass Phase, index for the table."
    ::= {xupsBypassEntry 1}

xupsBypassVoltage OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured UPS bypass voltage in volts."
    ::= {xupsBypassEntry 2}

xupsBypassId  OBJECT-TYPE
	SYNTAX     INTEGER {
		phase1toN (1),
		phase2toN (2),
		phase3toN (3),
		phase1to2 (4),
		phase2to3 (5),
		phase3to1 (6)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"value indicates what measurement is being stored in this table row :
		phase1 to neutral, phase2 to neutral, phase3 to neutral,
		phase1 to phase2, phase2 to phase3, phase3 to phase1. "
	::= { xupsBypassEntry 3 }

xupsBypassName  OBJECT-TYPE
	SYNTAX     OCTET STRING (SIZE(1..31))
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"A descriptive name for the phase."
	::= { xupsBypassEntry 4 }

xupsBypassCurrentHighPrecision OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS tenth of Amps"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured bypass current from the UPS meters in tenth of amps."
    ::= {xupsBypassEntry 5}

xupsBypassWatts OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured real bypass power in watts."
    ::= {xupsBypassEntry 6}

--
-- xupsBypassTotal group:
--
xupsBypassAverageVoltage OBJECT-TYPE
    SYNTAX     Integer32  (0..2147483647)  
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured bypass voltage from the UPS meters in volts.
         Related to the phase 1 if the UPS is single phase,
         either it is average of all the simple phase voltage."
    ::= {xupsBypassTotal 1}

xupsBypassTotalCurrent OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS tenth of Amps"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured bypass current from the UPS meters in tenth of amps.
         Related to the phase 1 if the UPS is single phase,
         either it is average of all the simple phase current."
    ::= {xupsBypassTotal 2}

xupsBypassTotalWatts OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured bypass active power in watts.
         Sum of all the simple phase watts."
    ::= {xupsBypassTotal 3}

xupsBypassTotalVA OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "VA"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The measured output apparent power in VA.
         Sum of all the simple phase VA."
    ::= {xupsBypassTotal 4}

xupsBypassAveragePowerFactor  OBJECT-TYPE
    SYNTAX     Integer32  
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION 
      "Indicates the total power factor of the input in hundredths.
       0.92 would be returned as 92."
    ::= { xupsBypassTotal 5 }


--
-- xupsEnvironment group:
--

xupsEnvAmbientTemp OBJECT-TYPE
    SYNTAX  Integer32 (-100..200)   
    UNITS       "degrees Centigrade"
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
       "The reading of the ambient temperature in the vicinity of the 
        UPS or SNMP agent."
    ::= { xupsEnvironment  1 }

xupsEnvAmbientLowerLimit OBJECT-TYPE
    SYNTAX  Integer32 (-100..200)
    UNITS       "degrees Centigrade"
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
       "The Lower Limit of the ambient temperature; if xupsEnvAmbientTemp 
        falls below this value, the xupsAmbientTempBad alarm will occur."
    ::= { xupsEnvironment  2 }

xupsEnvAmbientUpperLimit OBJECT-TYPE
    SYNTAX  Integer32 (-100..200)  
    UNITS       "degrees Centigrade"
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
       "The Upper Limit of the ambient temperature; if xupsEnvAmbientTemp 
        rises above this value, the xupsAmbientTempBad alarm will occur.
        This value should be greater than xupsEnvAmbientLowerLimit."
    ::= { xupsEnvironment  3 }

xupsEnvAmbientHumidity OBJECT-TYPE
    SYNTAX  Integer32 (0..100)   
    UNITS       "percent"
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
       "The reading of the ambient humidity in the vicinity of the 
        UPS or SNMP agent."
    ::= { xupsEnvironment  4 }

-- 
-- Moved the EMP-based objects, 
-- from xupsEnvRemoteTemp to xupsEnvRemoteHumidityUpperLimit
-- ( { xupsEnvironment  5 to 12 }, including xupsContactSenseTable,
-- to separate file Eaton-EMP-MIB.txt
--



--
-- xupsAlarm group:
--
xupsAlarms OBJECT-TYPE
    SYNTAX Gauge32
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The current number of alarm conditions."
    ::= {xupsAlarm 1}

xupsAlarmTable OBJECT-TYPE
    SYNTAX SEQUENCE OF XupsAlarmEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
       "A list of alarm table entries.  The number of entries
        is given by the value of xupsAlarms.
        Note that this table is sparsely (non-consecutively)
        numbered and will be empty if there are no active alarms."
    ::= {xupsAlarm 2}

xupsAlarmEntry OBJECT-TYPE
    SYNTAX XupsAlarmEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
        "Alarm Table Entry containing descriptive information 
         for one alarm entry."
    INDEX { xupsAlarmID }
    ::= {xupsAlarmTable 1}

XupsAlarmEntry ::= SEQUENCE {
        xupsAlarmID     Integer32,
        xupsAlarmDescr  OBJECT IDENTIFIER,
        xupsAlarmTime   TimeTicks
        }

xupsAlarmID OBJECT-TYPE
    SYNTAX     Integer32  (1..2147483647)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "A unique identifier for an alarm condition."
    ::= {xupsAlarmEntry 1}

xupsAlarmDescr OBJECT-TYPE
    SYNTAX     OBJECT IDENTIFIER
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "A reference to an alarm description object.  The object
         referenced should not be accessible, but rather be used to
         provide a unique description of the alarm condition."
    ::= {xupsAlarmEntry 2}

xupsAlarmTime OBJECT-TYPE
    SYNTAX     TimeTicks
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The value of the MIB-II variable sysUpTime when the alarm
         condition occurred."
    ::= {xupsAlarmEntry 3}

--
-- Well known alarm conditions.
--
xupsOnBattery                    OBJECT IDENTIFIER ::= {xupsAlarm 3}
xupsLowBattery                   OBJECT IDENTIFIER ::= {xupsAlarm 4}
xupsUtilityPowerRestored         OBJECT IDENTIFIER ::= {xupsAlarm 5}
xupsReturnFromLowBattery         OBJECT IDENTIFIER ::= {xupsAlarm 6}
xupsOutputOverload               OBJECT IDENTIFIER ::= {xupsAlarm 7}
xupsInternalFailure              OBJECT IDENTIFIER ::= {xupsAlarm 8}
xupsBatteryDischarged            OBJECT IDENTIFIER ::= {xupsAlarm 9}
xupsInverterFailure              OBJECT IDENTIFIER ::= {xupsAlarm 10}
xupsOnBypass                     OBJECT IDENTIFIER ::= {xupsAlarm 11}
xupsBypassNotAvailable           OBJECT IDENTIFIER ::= {xupsAlarm 12}
xupsOutputOff                    OBJECT IDENTIFIER ::= {xupsAlarm 13}
xupsInputFailure                 OBJECT IDENTIFIER ::= {xupsAlarm 14}
xupsBuildingAlarm                OBJECT IDENTIFIER ::= {xupsAlarm 15}
xupsShutdownImminent             OBJECT IDENTIFIER ::= {xupsAlarm 16}
xupsOnInverter                   OBJECT IDENTIFIER ::= {xupsAlarm 17}


xupsAlarmNumEvents OBJECT-TYPE
    SYNTAX     Gauge32 
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The number of entries in the UPS event history queue."
    ::= { xupsAlarm 18 }

xupsAlarmEventTable OBJECT-TYPE
    SYNTAX SEQUENCE OF XupsAlarmEventEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
        "A table of the UPS internal event history queue."
    ::= { xupsAlarm 19 }

xupsAlarmEventEntry OBJECT-TYPE
    SYNTAX XupsAlarmEventEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
        "One of the entries in the UPS event history queue."
    INDEX { xupsAlarmEventID }
    ::= { xupsAlarmEventTable 1 }

-- The first 4 vars in the xAEEntry have been deprecated, since they resulted in
-- a flood of difficult to interpret data.  They have been replaced by the single
-- entry, xupsAlarmEventMsg, which gives a human-readable description of the event.
XupsAlarmEventEntry ::= SEQUENCE {
        xupsAlarmEventID           Integer32,
        xupsAlarmEventDateAndTime  DisplayString,
        xupsAlarmEventKind         INTEGER,
        xupsAlarmEventDescr        Integer32,
        xupsAlarmEventMsg          DisplayString
        }

xupsAlarmEventID OBJECT-TYPE
    SYNTAX     Integer32 (1..400)
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
        "A unique number that reflects the order in which the event
         occurred. The oldest event in the queue will be number 1.
         Subsequent events will be numbered 2, 3, 4, etc."
    ::= { xupsAlarmEventEntry 1 }

xupsAlarmEventDateAndTime OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..22))
    MAX-ACCESS read-only
    STATUS     deprecated
    DESCRIPTION
        "The time and date that an event occurred as recorded in the UPS
         internal event queue.  This string will reflect the time and
         date as set in the UPS itself and will not be referenced to sysUpTime.
         The format is MM/DD/YYYY:HH:MM:SS.  Time is 24 hour standard."
    ::= { xupsAlarmEventEntry 2 }

xupsAlarmEventKind OBJECT-TYPE
    SYNTAX     INTEGER {
        occurred (1),
        cleared (2),
        unknown (3)
        }
    MAX-ACCESS read-only
    STATUS     deprecated
    DESCRIPTION
        "Enumerated value that tells whether the event is an
         occurrence of an alarm condition or a clearing of an
         alarm condition."
    ::= { xupsAlarmEventEntry 3 }

xupsAlarmEventDescr OBJECT-TYPE
    SYNTAX     Integer32  (0..2147483647)
    MAX-ACCESS read-only
    STATUS     deprecated
    DESCRIPTION
        "A description of the event stored in the UPS event queue.  
         This description will be a sixteen bit integer value 
         representing one of the defined alarms in the Powerware Binary 
         Computer Mode communication specification; for example,
         a value of 0 represents the 'Inverter AC Over Voltage'
         alarm (byte 1, bit 0 in the BCM Alarm Map)."
    ::= { xupsAlarmEventEntry 4 }

xupsAlarmEventMsg OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..80))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "A text string describing each entry in the Event Log.  The format of this
         text message is free (not fixed) for the operator to read; good contents 
         would be a time & date stamp, the event type, and a description of the event."
    ::= { xupsAlarmEventEntry 5 }

--
-- More Well known alarm conditions.
--
xupsBreakerOpen                  OBJECT IDENTIFIER ::= {xupsAlarm 20}
xupsAlarmEntryAdded              OBJECT IDENTIFIER ::= {xupsAlarm 21}
xupsAlarmEntryRemoved            OBJECT IDENTIFIER ::= {xupsAlarm 22}

-- Same as RFC 1628 Well Known Alarms:
xupsAlarmBatteryBad              OBJECT IDENTIFIER ::= {xupsAlarm 23}
xupsOutputOffAsRequested         OBJECT IDENTIFIER ::= {xupsAlarm 24}
xupsDiagnosticTestFailed         OBJECT IDENTIFIER ::= {xupsAlarm 25}
xupsCommunicationsLost           OBJECT IDENTIFIER ::= {xupsAlarm 26}
xupsUpsShutdownPending           OBJECT IDENTIFIER ::= {xupsAlarm 27}
xupsAlarmTestInProgress          OBJECT IDENTIFIER ::= {xupsAlarm 28}

-- Alarm for the Ambient Temperature, when outside of lo/hi limits
xupsAmbientTempBad               OBJECT IDENTIFIER ::= {xupsAlarm 29}

-- For Loss of Redundancy in parallel systems
xupsLossOfRedundancy             OBJECT IDENTIFIER ::= {xupsAlarm 30}

-- More Same as RFC 1628 Well Known Alarms:
xupsAlarmTempBad                 OBJECT IDENTIFIER ::= {xupsAlarm 31}
xupsAlarmChargerFailed           OBJECT IDENTIFIER ::= {xupsAlarm 32}
xupsAlarmFanFailure              OBJECT IDENTIFIER ::= {xupsAlarm 33}
xupsAlarmFuseFailure             OBJECT IDENTIFIER ::= {xupsAlarm 34}

-- A Relay, Contactor, or Breaker has failed
xupsPowerSwitchBad               OBJECT IDENTIFIER ::= {xupsAlarm 35}

-- One module in a parallel or composite system has failed
xupsModuleFailure                OBJECT IDENTIFIER ::= {xupsAlarm 36}

-- Two Alarms for systems with an Alternate Power Source, such as 
-- Secondary utility feed (on a dual AC input UPS), generator,
-- flywheel, or fuelcell. Enabled by xupsSecondaryInputWatch.
xupsOnAlternatePowerSource       OBJECT IDENTIFIER ::= {xupsAlarm 37}
xupsAltPowerNotAvailable         OBJECT IDENTIFIER ::= {xupsAlarm 38}

-- Some Notice condition exists which is not covered by the other WKA
-- (like an xupsInternalFailure, but at a lower level of urgency)
xupsNoticeCondition              OBJECT IDENTIFIER ::= {xupsAlarm 39}

-- Alarms for the Remote Temperature & Humidity, when outside of lo/hi limits
xupsRemoteTempBad                OBJECT IDENTIFIER ::= {xupsAlarm 40}
xupsRemoteHumidityBad            OBJECT IDENTIFIER ::= {xupsAlarm 41}

-- Last of the RFC1628 Well Known Alarms:
xupsAlarmOutputBad               OBJECT IDENTIFIER ::= {xupsAlarm 42}
xupsAlarmAwaitingPower           OBJECT IDENTIFIER ::= {xupsAlarm 43}

-- Alarm for this important UPS mode
xupsOnMaintenanceBypass          OBJECT IDENTIFIER ::= {xupsAlarm 44}

-- New alarms now managed by the Network-M2 card
xupsOutputNotProtected           OBJECT IDENTIFIER ::= {xupsAlarm 51}


--
-- xupsTest group:
--

xupsTestStart OBJECT-TYPE           
    SYNTAX     INTEGER { 
        testBattery (1),            
        noTestStarted (2),          
        testSystem (3),             
        testSecondarySource (4),    
        flashLightsTest (5),        
        cancelTest (6)              
        }
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "Setting this object initiates the requested Test.
		The test types which a UPS might support are 'testBattery', 
		'testSystem' (a UPS General Systems test, however defined by the UPS), 
		'testSecondarySource' (test if the Secondary power source is good on a 
		dual input UPS), and 
		'flashLightsTest' (start a test which flashes the UPS lights, and if 
		available, sounds the horn to help locate the UPS).
        If a UPS does not support the requested test, the set operation may 
		succeed but the xupsTestBatteryStatus will end up as notSupported.
        When read, this object indicates the last test requested via this object, 
		if any; 'noTestStarted' could be the initial value.
        Currently only the 'flashLightsTest' can be canceled with 'cancelTest'."
    ::= {xupsTest 1}

xupsTestBatteryStatus OBJECT-TYPE
    SYNTAX     INTEGER {
        unknown (1),
        passed (2),
        failed (3),
        inProgress (4),
        notSupported (5),
        inhibited (6),
        scheduled (7)
        }
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "Reading this enumerated value gives an indication of the (last) 
         UPS Battery test status.
		 'inhibited' means that the battery test could not be run.
		 'scheduled' means that the battery test could not be run at the time
		 of request, but will be run at some later (UPS-determined) time."
    ::= {xupsTest 2}

xupsLastGeneralTest OBJECT-TYPE           
    SYNTAX     INTEGER { 
        noTestStarted (2),                    
        testSystem (3),             
        testSecondarySource (4),    
        flashLightsTest (5)         
        }
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "Indicates the last UPS test requested via xupsTestStart or by other 
         non-SNMP means, other than for the testBattery (1) case.
         The results of the test indicated by this object are reported in 
         xupsLastGeneralTestResult."
    ::= {xupsTest 3}

xupsLastGeneralTestResult OBJECT-TYPE
    SYNTAX     INTEGER {
        unknown (1),
        passed (2),
        failed (3),
        inProgress (4),
        notSupported (5),
        inhibited (6),
        scheduled (7)
        }
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "Reading this enumerated value gives the result of the test indicated
         in xupsLastGeneralTest."
    ::= {xupsTest 4}

xupsTestTrap OBJECT-TYPE           
    SYNTAX INTEGER { startTestTrap (1) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
      	"Setting startTestTrap to 1 will initiate a test trap 
	       to be sent out from the agent.  All other set values are invalid."
    ::= {xupsTest 5}


--
-- xupsControl group:
--
xupsControlOutputOffDelay OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647) 
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "Setting this value to other than zero will cause the UPS
         output to turn off after the number of seconds.
         Setting it to 0 will cause an attempt to abort a pending
         shutdown."
    ::= {xupsControl 1}

xupsControlOutputOnDelay OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)    
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "Setting this value to other than zero will cause the UPS
         output to turn on after the number of seconds.
         Setting it to 0 will cause an attempt to abort a pending
         startup."
    ::= {xupsControl 2}

xupsControlOutputOffTrapDelay OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)    
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "When xupsControlOutputOffDelay reaches this value, a trap will
         be sent."
    ::= {xupsControl 3}

xupsControlOutputOnTrapDelay OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS deprecated
    DESCRIPTION
        "When xupsControlOutputOnDelay reaches this value, a
         xupsOutputOff trap will be sent."
    ::= {xupsControl 4}

xupsControlToBypassDelay OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "Setting this value to other than zero will cause the UPS
         output to go to Bypass after the number of seconds.
         If the Bypass is unavailable, this may cause the UPS
         to not supply power to the load.
         Setting it to 0 will cause an attempt to abort a pending
         shutdown."
    ::= {xupsControl 5}

xupsLoadShedSecsWithRestart OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
       "Setting this value will cause the UPS output to turn off 
        after the set number of seconds, then restart (after a UPS-defined
        'down time') when the utility is again available.  
        Unlike xupsControlOutputOffDelay, which might or might not,
        this object always maps to the XCP 0x8A Load Dump & Restart command,
        so the desired shutdown and restart behavior is guaranteed to happen.
        Once set, this command cannot be aborted.
        This is the preferred Control object to use when performing 
        an On Battery OS Shutdown."
    ::= {xupsControl 6}

xupsSwitchable  OBJECT-TYPE
	SYNTAX     INTEGER {
		switchable (1),
		notSwitchable (2)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Parameter which indicates whether UPS commands received via any 
		 communication path (aside from manual controls) are able (switchable) 
		 or not able (notSwitchable) to control the UPS."
	::= { xupsControl 7 }

--
-- xupsConfig group:
--
xupsConfigOutputVoltage OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The nominal UPS Output voltage per phase in volts."
    ::= {xupsConfig 1}

xupsConfigInputVoltage OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)  
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The nominal UPS Input voltage per phase in volts."
    ::= {xupsConfig 2}

xupsConfigOutputWatts OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The nominal UPS available real power output in watts."
    ::= {xupsConfig 3}

xupsConfigOutputFreq OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "0.1 Hertz"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The nominal output frequency in tenths of Hz."
    ::= {xupsConfig 4}

xupsConfigDateAndTime OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..22))
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "Date and time information for the UPS.  Setting this variable
         will initiate a set UPS date and time to this value.  Reading
         this variable will return the UPS time and date.  This value
         is not referenced to sysUpTime.  It is simply the clock value
         from the UPS real time clock.
         Format is as follows: MM/DD/YYYY:HH:MM:SS."
    ::= { xupsConfig 5 }

xupsConfigLowOutputVoltageLimit OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647) 
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The Lower limit for acceptable Output Voltage, per the UPS
         specifications."
    ::= {xupsConfig 6}

xupsConfigHighOutputVoltageLimit OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The Upper limit for acceptable Output Voltage, per the UPS
         specifications."
    ::= {xupsConfig 7}

xupsConfigInstallDate OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..16))
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "The date when this UPS was installed.  Free text format, so the 
         preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc)."
    ::= {xupsConfig 8}



--
-- xupsTrapControl group:
--
xupsMaxTrapLevel OBJECT-TYPE
    SYNTAX     INTEGER {
        none     (1),
        critical (2),
        major    (3),
        minor    (4),
        allTraps (5)
        }
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "The level of severity of traps which will be sent to the
         requesting host; individual trap receivers will have
         individual values for this variable.  Values are:
         (1) none: no traps will be sent to this host;
         (2) critical: only traps for Critical alarm conditions will
             be sent to this host;
         (3) major: Critical and Major traps will be sent;
         (4) minor: All levels of alarming traps will be sent: Critical, 
             Major, and Minor
            (This level was added in PowerMIB v3.11)
         (5) allTraps: all Traps will be sent to this host
            (Critical, Major, Minor, Informational)."
    ::= {xupsTrapControl 1}

xupsSendTrapType OBJECT-TYPE
    SYNTAX     INTEGER {
        stnd     (1),       
        xups     (2),       
        stndPlus (3),       
        xupsPlus (4),       
		pxg      (5)        
        }
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "The type of traps which will be sent to the
         requesting host; individual trap receivers will have
         individual values for this variable.  The additional
         variables in types (3) and (4) are useful for determining
         which UPS is the source on multi-port network adapters,
         and for getting additional descriptive information.
         Types (1) through (4) are all SNMP version 1 trap PDUs.
         Values are:
         (1) stnd: Traps as defined in the Standard UPS MIB (RFC1628)
            and Generic (MIB II) traps as defined in RFC 1215.
         (2) xups: xupsTrapDefined Traps as defined in the PowerMIB
            and Generic (MIB II) traps as defined in RFC 1215.
         (3 Deprecated) stndPlus: same as stnd plus variables from the interface
            group and, where appropriate, xupsTrapMessage.
         (4 Deprecated) xupsPlus: xupsTrapPortN Traps (same as xups plus 
            variables from the interface group) and, 
            for authFail, xupsTrapMessage.
         (5 pxg: Traps as defined in the Power Xpert Gateway MIB
            (PXG-MIB)."
    ::= {xupsTrapControl 2}

xupsTrapMessage OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..79))
    MAX-ACCESS read-only            -- actually not-accessible
    STATUS     current
    DESCRIPTION
        "A descriptive text message which may be sent with traps to
         further explain the reason for the trap.
         This object is not-accessible to MIB browsers, but had to be changed to
         read-only to satisfy SMIv2 syntax checkers since it is included in traps."
    ::= {xupsTrapControl 3}

-- An Identifier for the PowerMIB traps
-- Used below in the section where the traps are defined
xupsTrapSource   OBJECT IDENTIFIER       ::= {xupsTrapControl 4}

xupsHeartbeatMinsInterval OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "Minutes"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
        "How often to send the xupstdHeartbeat trap, in units of minutes.
         A setting of 0 disables the Heartbeat function."
    ::= {xupsTrapControl 5}



--
-- xupsRecep group:
--
-- (Note that the terms Receptacle, Outlet, and Load Group are used interchangeably
--  here and all mean "one of a group of controllable, power-switched outputs")
--
xupsNumReceptacles OBJECT-TYPE
    SYNTAX     Integer32 (0..64)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The number of independently controllable Receptacles, as described in the 
         xupsRecepTable."
    ::= {xupsRecep 1}
    
xupsRecepTable OBJECT-TYPE
    SYNTAX SEQUENCE OF XupsRecepEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
       "A list of receptacle table entries.  The number of entries
        is given by the value of xupsNumReceptacles."
    ::={xupsRecep 2}
    
xupsRecepEntry OBJECT-TYPE
    SYNTAX XupsRecepEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION 
        "A receptacle table entry containing the status and
         control values for one receptacle."
    INDEX { xupsRecepIndex }
    ::= { xupsRecepTable 1 }

XupsRecepEntry ::= SEQUENCE {
        xupsRecepIndex               Integer32,
        xupsRecepStatus              INTEGER,
        xupsRecepOffDelaySecs        Integer32,
        xupsRecepOnDelaySecs         Integer32,
        xupsRecepAutoOffDelay        Integer32,
        xupsRecepAutoOnDelay         Integer32,
        xupsRecepShedSecsWithRestart Integer32, 
        xupsRecepHourlyPowerUsage    Integer32,
        xupsRecepCumulativePowerUsage Integer32,
        xupsRecepCumulativePowerUsageTimer Counter32
		}
    
xupsRecepIndex OBJECT-TYPE
    SYNTAX     Integer32 (1..64)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The number of the Receptacle. Serves as index for Receptacle table."
    ::= {xupsRecepEntry 1}
    

xupsRecepStatus OBJECT-TYPE
    SYNTAX     INTEGER {
        on(1), off(2), pendingOff(3), pendingOn(4), unknown(5), 
        reserved(6), failedClosed(7), failedOpen(8) }
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 
         4=Off w/Pending ON, 5=Unknown, 6=Reserved for future, 
         7=Failed in Closed position, 8=Failed in Open position."
    ::={xupsRecepEntry 2}
            

xupsRecepOffDelaySecs OBJECT-TYPE
    SYNTAX     Integer32 (-1..2147483647) 
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
       "The Delay until the Receptacle is turned Off.  Setting 
        this value to other than -1 will cause the UPS output to 
        turn off after the number of seconds (0 is immediately).  
        Setting it to -1 will cause an attempt to abort a pending shutdown.
        When this object is set while the UPS is On Battery, it is not necessary
        to set xupsRecepOnDelaySecs, since the outlet will turn back on 
        automatically when power is available again."
    ::= {xupsRecepEntry 3}

xupsRecepOnDelaySecs OBJECT-TYPE
    SYNTAX     Integer32 (-1..2147483647) 
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
       "The Delay until the Receptacle is turned On.  Setting 
        this value to other than -1 will cause the UPS output to 
        turn on after the number of seconds (0 is immediately).  
        Setting it to -1 will cause an attempt to abort a pending restart."
    ::={xupsRecepEntry 4}


xupsRecepAutoOffDelay OBJECT-TYPE
    SYNTAX     Integer32 (-1..32767) 
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
       "The delay after going On Battery until the Receptacle is 
        automatically turned Off.  A value of -1 means that this Output should 
        never be turned Off automatically, but must be turned Off only by command.
        Values from 0 to 30 are valid, but probably innappropriate.
        The AutoOffDelay can be used to prioritize loads in the event of a prolonged 
        power outage; less critical loads will turn off earlier to extend battery 
        time for the more critical loads. If the utility power is restored before the 
        AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off."
    ::= {xupsRecepEntry 5}
    
xupsRecepAutoOnDelay OBJECT-TYPE
    SYNTAX     Integer32 (-1..32767)
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
       "Seconds delay after the Outlet is signaled to turn On before the Output is
        Automatically turned ON. A value of -1 means that this Output should never
        be turned On automatically, but only when specifically commanded to do so.
        A value of 0 means that the Receptacle should come On immediately
        at power-up or for an On command."
    ::= {xupsRecepEntry 6}

-- xupsRecepAutoOnDelay has three purposes: 
-- 1. To coordinate the automatic startup of various outlets, when the normal 
-- auto-sequencing of 1 second per outlet is not adequate. For example, they may 
-- be used to power up hard disk arrays before CPU units are started. 
-- 2. To force additional 'Down Time' during xupsRecepOffDelaySecs commands, for 
-- equipment to be reset, when the standard 'Down Time' is not long enough. 
-- 3. For the -1 value, to ensure that loads won't be powered until commanded, 
-- following power-up or a xupsRecepOffDelaySecs command.

xupsRecepShedSecsWithRestart OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
       "Setting this value will cause the UPS output to turn off 
        after the set number of seconds, then restart (after a UPS-defined
        'down time') when the utility is again available.  
        Unlike xupsRecepOffDelaySecs, which might or might not,
        this object always maps to the XCP 0x8A Load Dump & Restart command,
        so the desired shutdown and restart behavior is guaranteed to happen.
        Once set, this command cannot be aborted."
    ::= {xupsRecepEntry 7}

xupsRecepHourlyPowerUsage  OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "Wh"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Units are Watt-hours.This is the energy consumed during the last hour."
	::= { xupsRecepEntry 8 }

xupsRecepCumulativePowerUsage  OBJECT-TYPE
    SYNTAX     Integer32 (0..2147483647)
    UNITS      "Wh"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Units are Watt-hours.This is the energy consumed since the last reset.
         This object is writable so that it can be reset to 0.
         When it is written to 0, the xupsRecepCumulativePowerUsageTimer will be reset to 0 as well."
	::= { xupsRecepEntry 9 }

xupsRecepCumulativePowerUsageTimer  OBJECT-TYPE
    SYNTAX     Counter32
    UNITS      "Seconds"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Time in seconds since the cumulative power usage was last reset."
	::= { xupsRecepEntry 10 }


--
-- xupsTopology group:
--
xupsTopologyType OBJECT-TYPE
    SYNTAX     Integer32 (0..32767)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
       "Value which denotes the type of UPS by its power topology.  Values are the
        same as those described in the XCP Topology block's Overall Topology field."
    ::= {xupsTopology 1}

xupsTopoMachineCode OBJECT-TYPE
    SYNTAX     Integer32 (0..32767)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
       "ID Value which denotes the Powerware model of the UPS for software.  
        Values are the same as those described in the XCP Configuration 
        block's Machine Code field."
    ::= {xupsTopology 2}

xupsTopoUnitNumber OBJECT-TYPE
    SYNTAX     Integer32 (0..64)
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
       "Identifies which unit and what type of data is being reported.
        A value of 0 means that this MIB information comes from the top-level system 
        view (eg, manifold module or system bypass cabinet reporting total system 
        output).  Standalone units also use a value of 0, since they are the 'full 
        system' view.
        A value of 1 or higher indicates the number of the module in the system
        which is reporting only its own data in the PowerMIB objects."
    ::= {xupsTopology 3}

xupsTopoPowerStrategy OBJECT-TYPE
    SYNTAX     INTEGER {
        highAlert(1), standard(2), enableHighEfficiency(3),
        immediateHighEfficiency(4) }
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
       "Value which denotes which Power Strategy is currently set for the UPS.
        The values are:
        highAlert(1) - The UPS shall optimize its operating state to maximize its 
                power-protection levels.  This mode will be held for at most 24 hours.
        standard(2) - Balanced, normal power protection strategy. UPS will not enter 
                HE operating mode from this setting.
        enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to 
                optimize its operating state to maximize its efficiency, when 
                conditions change to permit it (as determined by the UPS).
        forceHighEfficiency(4) - If this value is permitted to be Set for this UPS,
                and if conditions permit, requires the UPS to enter High Efficiency 
                mode now, without delay (for as long as utility conditions permit).
                After successfully set to forceHighEfficiency(4), 
                xupsTopoPowerStrategy changes to value enableHighEfficiency(3).
        xupsOutputSource will indicate if the UPS status is actually operating in 
        High Efficiency mode."
    ::= {xupsTopology 4}


--
-- xupsAgent group:
--
xupsAgentManufacturer OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..31))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The card agent Manufacturer Name (e.g. Eaton Corporation)."
    ::= { xupsAgent 1}

xupsAgentModel OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..63))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The card agent model"
    ::= {xupsAgent 2}

xupsAgentSoftwareVersion OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..63))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
        "The agent firmware version."
    ::= {xupsAgent 3}

xupsAgentPartNumber  OBJECT-TYPE
    SYNTAX     OCTET STRING (SIZE(1..31))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION 
        "The card agent catalog part number."
    ::= { xupsAgent 4 }

xupsAgentSerialNumber  OBJECT-TYPE
    SYNTAX     OCTET STRING (SIZE(1..31))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION 
        "The card agent catalog serial number."
    ::= { xupsAgent 5 }


-- *************************************************************************
-- *************************************************************************

--
-- Traps (xupst)
--
-- 1) Eaton's traps have been defined in this MIB for three different sources.
--    The trap definitions for the three sources are very similar,
--      and use the same alarms as their triggers; their names are prefaced
--      by xupstb, xupstd, and xupstp to distinguish the three types
--      However, the products that the "Basic" and "Port Defined" trap types were
--      created for have been obsoleted, so the only trap types in active use 
--      are the "Defined" (xupstd) traps listed below
--      The Obsolete types have been moved to file XUPS_Obsolete.mib
--
--      a) OBSOLETE - Basic Agents for which the trap variables have not been 
--              defined, though trap variables are included with the trap PDU
--      xupsNull         OBJECT IDENTIFIER       ::= { xupsMIB 0 }
--      xupsTrapBasic    OBJECT IDENTIFIER       ::= { xupsNull 0 }
--

--      b) Agents with exactly Defined trap variables, which may be
--              used as input to trap response macros on management stations
--      This trap type is selected by setting xupsSendTrapType to xups(2)
xupsTrapDefined  OBJECT IDENTIFIER       ::= {xupsTrapSource 1}
--      Following the recommendations for coexistence between v1 traps
--      and v2 notifications, define the snmpTrapOID base with a 0
xupsTrapOidDefined OBJECT IDENTIFIER     ::= { xupsTrapDefined 0 }

--
--      c) OBSOLETE - Agents with Defined traps including ifIndex and ifDescr,
--              which can be used to determine which UPS of a multi-port
--              agent (eg, Eaton Network SNMP Adapter) sent the trap
--      This trap type was selected by setting xupsSendTrapType to xupsPlus(4)
--      xupsTrapPortN    OBJECT IDENTIFIER       ::= {xupsTrapSource 2}
--
-- 2) Trap Severity Level is given as a comment to indicate which 
--      xupsMaxTrapLevel will result in this trap being sent;  
--      levels are (in order): Critical, Major, Minor, Informational
--


-- ****************************************************************************
-- ****************************************************************************
--
-- Traps from xupsTrapDefined source (xupstd):
--

xupstdControlOff NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The UPS output power will turn off in a number of
    seconds equal to upsControlOutputOffTrapDelay."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 1 }

xupstdControlOn NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The UPS output power will turn on in a number of
    seconds equal to upsControlOutputOnTrapDelay."
    --#SEVERITY INFORMATIONAL
    ::= { xupsTrapOidDefined 2 }

xupstdOnBattery NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The UPS has no AC input power and is running on 
     battery."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 3 }

xupstdLowBattery NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The UPS batteries are low.  Tied to low battery 
    alarm condition."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 4 }

xupstdUtilityPowerRestored NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "Input power has been restored after running on battery."
    --#SEVERITY INFORMATIONAL
    ::= { xupsTrapOidDefined 5 }

xupstdReturnFromLowBattery NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The battery has recovered from a low battery condition."
    --#SEVERITY INFORMATIONAL
    ::= { xupsTrapOidDefined 6 }

xupstdOutputOverload NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The ups has sensed an overload of greater than 
     106 percent.  Tied to the 106% overload alarm."
    --#SEVERITY MINOR 
    ::= { xupsTrapOidDefined 7 }

xupstdInternalFailure NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "Some component of the ups - rectifier, inverter,
     control panel has failed.  Tied to alarms indi-
     cating failure."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 8 }

xupstdBatteryDischarged NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The Battery Totally Discharged Alarm has occurred."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 9 }

xupstdInverterFailure NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The ups inverter is unavailable or malfunctioning due to an internal failure."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 10 }

xupstdOnBypass NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The ups has gone on bypass for some reason."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 11 }

xupstdBypassNotAvailable NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The ups bypass is unavailable"
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 12 }

xupstdOutputOff NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The ups output is switched off."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 13 }

xupstdInputFailure NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The ups input power is incorrect in voltage,
     frequency, or phase rotation."
    --#SEVERITY MINOR 
    ::= { xupsTrapOidDefined 14 }

xupstdBuildingAlarm NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "One of the defined building alarms has occurred."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 15 }

xupstdShutdownImminent NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The ups shutdown imminent alarm has occurred." 
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 16 }

xupstdOnInverter NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The ups is returned to utility power running the inverter 
     after either a transfer to bypass or a run on battery."
    --#SEVERITY INFORMATIONAL
    ::= { xupsTrapOidDefined 17 }
    
xupstdBreakerOpen NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "One of the UPS breakers or contactors has been opened."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 20 }
    
xupstdAlarmEntryAdded NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "An alarm not defined in the xups Well Known Alarms
     (eg, an alarm defined in RFC1628)
     has been added to the Alarm Table."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 21 }
    
xupstdAlarmEntryRemoved NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "An alarm not defined in the xups Well Known Alarms
     has been removed from the Alarm Table."
    --#SEVERITY INFORMATIONAL 
    ::= { xupsTrapOidDefined 22 }

xupstdAlarmBatteryBad        NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "One or more batteries have been determined to require replacement."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 23 }

xupstdOutputOffAsRequested   NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The UPS has shutdown as requested, i.e., the output is off."
    --#SEVERITY INFORMATIONAL 
    ::= { xupsTrapOidDefined 24 }

xupstdDiagnosticTestFailed   NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The result of the last diagnostic test indicates a failure."
    --#SEVERITY MINOR 
    ::= { xupsTrapOidDefined 25 }

xupstdCommunicationsLost     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "A problem has been encountered in the communications
     between the agent and the UPS."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 26 }

xupstdUpsShutdownPending     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "An xupsControlOutputOffDelay countdown is underway."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 27 }

xupstdAlarmTestInProgress    NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "A test is in progress, as initiated and indicated by the xupsTest Group.  
     When the test is complete, one of the following traps will be sent:
     - xupstdDiagnosticTestFailed if the test fails,
     - xupstdDiagnosticTestPassed on success, or
     - xupstdAlarmEntryRemoved in other cases (e.g., Test Canceled)."
    --#SEVERITY INFORMATIONAL 
    ::= { xupsTrapOidDefined 28 }

-- Provide additional information with the AmbientTemp trap
xupstdAmbientTempBad         NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
                 xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit, 
                 xupsEnvAmbientUpperLimit }
    STATUS     current
    DESCRIPTION
       "The ambient temperature, xupsEnvAmbientTemp, has fallen below 
    the set lower limit, xupsEnvAmbientLowerLimit, or has risen above 
    the set upper limit, xupsEnvAmbientUpperLimit." 
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 29 }

-- Added to support the ConnectUPS Web/SNMP card's ability to monitor contact(s)
xupstdContactActiveNotice NOTIFICATION-TYPE
    OBJECTS    { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
    STATUS     current
    DESCRIPTION
    "The Contact indicated by xupsContactIndex is in its Active state.
     The following are the situations that generate this trap:
        For xupsContactType:    and     xupsContactState: 
            normallyOpen(1)     and     closedWithNotice(4)
            normallyClosed(2)   and     openWithNotice(3)
            anyChange(3)        and     openWithNotice(3) or closedWithNotice(4)"
    --#SEVERITY MAJOR
    ::= { xupsTrapOidDefined 30 }

xupstdContactInactiveNotice NOTIFICATION-TYPE
    OBJECTS    { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
    STATUS     current
    DESCRIPTION
    "The Contact indicated by xupsContactIndex has changed to its Inactive state."
    --#SEVERITY INFORMATIONAL
    ::= { xupsTrapOidDefined 31 }


xupstdLossOfRedundancy     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "A parallel UPS system is no longer operating in N+1 redundant mode;
       this may be due to module failure or removal, or due to overloading."
    --#SEVERITY MINOR 
    ::= { xupsTrapOidDefined 32 }

xupstdAlarmTempBad     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "An internal temperature is out of tolerance."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 33 }

xupstdAlarmChargerFailed     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "An uncorrected problem has been detected within the UPS charger subsystem."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 34 }

xupstdAlarmFanFailure     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The failure of one or more fans in the UPS has been detected."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 35 }

xupstdAlarmFuseFailure     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The failure of one or more fuses has been detected."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 36 }

xupstdPowerSwitchBad     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "A Relay, Contactor, or Breaker has failed."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 37 }

xupstdModuleFailure     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "One module in a parallel or composite system has failed."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 38 }

-- xupsInputSource added to this trap's var list
xupstdOnAlternatePowerSource     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, xupsInputSource }
    STATUS     current
    DESCRIPTION
    "The system is being powered by its Alternate Power Source, such as a 
     Secondary utility feed (on a dual AC input UPS), generator, flywheel, 
     or fuel cell."
    --#SEVERITY MINOR 
    ::= { xupsTrapOidDefined 39 }

xupstdAltPowerNotAvailable     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "On systems with a separate alternate power source (eg, dual AC inputs), 
     that alternate power source is currently not available.  This could be 
     a problem if the primary power source (eg, utility) fails for a period 
     of time longer than that for which the internal batteries can supply power."
    --#SEVERITY MINOR 
    ::= { xupsTrapOidDefined 40 }

xupstdNoticeCondition     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "Some Notice condition exists which is not covered by the other traps.
     This is like an xupstdInternalFailure, but at a lower severity level."
    --#SEVERITY MINOR 
    ::= { xupsTrapOidDefined 41 }


-- Added to provide additional information with the RemoteTemp and RemoteHumidity 
xupstdRemoteTempBad         NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
                 xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit, 
                 xupsEnvRemoteTempUpperLimit }
    STATUS     current
    DESCRIPTION
       "The remote temperature, xupsEnvRemoteTemp, has fallen below 
    the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above 
    the set upper limit, xupsEnvRemoteTempUpperLimit." 
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 42 }

xupstdRemoteHumidityBad     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
                 xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit, 
                 xupsEnvRemoteHumidityUpperLimit }
    STATUS     current
    DESCRIPTION
       "The remote temperature, xupsEnvRemoteHumidity, has fallen below 
    the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above 
    the set upper limit, xupsEnvRemoteHumidityUpperLimit." 
    --#SEVERITY MINOR 
    ::= { xupsTrapOidDefined 43 }


xupstdHeartbeat NOTIFICATION-TYPE
    OBJECTS    { xupsInputSource,  xupsOutputSource, xupsAlarms }
    STATUS     current
    DESCRIPTION
    "A periodic status trap message.  It is sent at an interval
    set by object xupsHeartbeatMinsInterval.
    The included variables provide a brief statement of the UPS status."
    --#SEVERITY INFORMATIONAL
    ::= { xupsTrapOidDefined 44 }

xupstdDiagnosticTestPassed   NOTIFICATION-TYPE
    OBJECTS    { xupsTestBatteryStatus,  xupsLastGeneralTest, xupsLastGeneralTestResult }
    STATUS     current
    DESCRIPTION
    "A diagnostic test just completed, and its result is Passed.
    The included variables provide additional information on the test."
    --#SEVERITY INFORMATIONAL
    ::= { xupsTrapOidDefined 45 }

xupstdOutputBad     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The output condition (other than OutputOverload) is out of tolerance."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 46 }

xupstdAwaitingPower     NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The UPS output is off and the UPS is awaiting the return of input power."
    --#SEVERITY MINOR 
    ::= { xupsTrapOidDefined 47 }

xupstdOnMaintenanceBypass NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The UPS has been placed on Maintenance / Manual Bypass by an operator."
    --#SEVERITY MAJOR 
    ::= { xupsTrapOidDefined 48 }

xupstdCommEstablished  NOTIFICATION-TYPE
    OBJECTS    { xupsIdentModel,  xupsOutputSource }
    STATUS     current
    DESCRIPTION
    "This trap is sent when the SNMP agent first establishes a communication 
     link with the UPS.
     The included variables provide identification and UPS status information."
    --#SEVERITY INFORMATIONAL
    ::= { xupsTrapOidDefined 49 }

xupstdAgentDown  NOTIFICATION-TYPE
    -- OBJECTS   { (none) }
    STATUS     current
    DESCRIPTION
    "This trap is sent when the SNMP agent is exiting or closing down gracefully.
     This may be triggered by a signal from the OS to stop this process.  In many
     implementations, it will be followed quickly by a restart of this vital process."
    --#SEVERITY MINOR
    ::= { xupsTrapOidDefined 50 }

-- New traps now managed by the Network-M2 card
xupstdOutputNotProtected  NOTIFICATION-TYPE
    OBJECTS    { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "The ups output is not protectet for any reason in the UPS."
    --#SEVERITY CRITICAL 
    ::= { xupsTrapOidDefined 51 }

xupstdTestTrap  NOTIFICATION-TYPE
    OBJECTS    { sysName, xupsTrapMessage }
    STATUS     current
    DESCRIPTION
    "This trap is sent to the trap receivers to check proper reception of traps."
    --#SEVERITY INFORMATIONAL
    ::= { xupsTrapOidDefined 100 }

--
-- Conformance-related definitions
-- (Defined mostly to satisfy the MIB checkers.)
--
xupsConformance OBJECT IDENTIFIER ::= { xupsMIB 100 }

xupsIdentFullGroup  OBJECT-GROUP
    OBJECTS { xupsIdentManufacturer, xupsIdentModel, 
              xupsIdentSoftwareVersion, xupsIdentOemCode,
              xupsIdentPartNumber, xupsIdentSerialNumber }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsIdent subgroup objects."
    ::= { xupsConformance 2 }

xupsBatteryFullGroup  OBJECT-GROUP
    OBJECTS { xupsBatTimeRemaining, xupsBatVoltage, xupsBatCurrent, 
              xupsBatCapacity, xupsBatteryAbmStatus, xupsBatteryLastReplacedDate,
              xupsBatteryFailure, xupsBatteryNotPresent, xupsBatteryAged, xupsBatteryLowCapacity }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsBattery subgroup objects."
    ::= { xupsConformance 3 }

xupsInputFullGroup  OBJECT-GROUP
    OBJECTS { xupsInputFrequency, xupsInputLineBads, xupsInputNumPhases, 
              xupsInputSource, xupsDualInputStatus, xupsSecondaryInputWatch, xupsInputStatus }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsInput subgroup objects."
    ::= { xupsConformance 4 }

xupsInputTableFullGroup  OBJECT-GROUP
    OBJECTS { xupsInputPhase, xupsInputVoltage, xupsInputCurrent, xupsInputWatts,
              xupsInputId, xupsInputName, xupsInputCurrentHighPrecision }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsInputTable subgroup objects."
    ::= { xupsConformance 5 }

xupsOutputFullGroup  OBJECT-GROUP
    OBJECTS { xupsOutputLoad, xupsOutputFrequency, xupsOutputNumPhases, xupsOutputSource,
              xupsOutputHourlyPowerUsage, xupsOutputCumulativePowerUsage, xupsOutputCumulativePowerUsageTimer, xupsOutputStatus }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsOutput subgroup objects."
    ::= { xupsConformance 6 }

xupsOutputTableFullGroup  OBJECT-GROUP
    OBJECTS { xupsOutputPhase, xupsOutputVoltage, xupsOutputCurrent, xupsOutputWatts,
              xupsOutputId, xupsOutputName, xupsOutputCurrentHighPrecision, xupsOutputPercentLoad, xupsOutputVA }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsOutputTable subgroup objects."
    ::= { xupsConformance 7 }

xupsBypassFullGroup  OBJECT-GROUP
    OBJECTS { xupsBypassFrequency, xupsBypassNumPhases, xupsBypassPhase, xupsBypassVoltage }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsBypass subgroup objects."
    ::= { xupsConformance 8 }

xupsEnvironmentFullGroup  OBJECT-GROUP
    OBJECTS { xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit, 
              xupsEnvAmbientUpperLimit, xupsEnvAmbientHumidity }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsEnvironment subgroup objects."
    ::= { xupsConformance 9 }

xupsAlarmFullGroup  OBJECT-GROUP
    OBJECTS { xupsAlarms, xupsAlarmID, xupsAlarmDescr, xupsAlarmTime }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsAlarm subgroup objects."
    ::= { xupsConformance 10 }

xupsAlarmEventsFullGroup  OBJECT-GROUP
    OBJECTS { xupsAlarmNumEvents, xupsAlarmEventMsg }
    STATUS  current
    DESCRIPTION
        "The Full set of Alarm/Event history subgroup objects."
    ::= { xupsConformance 11 }

xupsTestFullGroup  OBJECT-GROUP
    OBJECTS { xupsTestStart, xupsTestBatteryStatus, xupsLastGeneralTest,
              xupsLastGeneralTestResult, xupsTestTrap }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsTest subgroup objects."
    ::= { xupsConformance 12 }

xupsControlFullGroup  OBJECT-GROUP
    OBJECTS { xupsControlOutputOffDelay, xupsControlOutputOnDelay, 
              xupsControlOutputOffTrapDelay, xupsControlToBypassDelay, 
              xupsLoadShedSecsWithRestart, xupsSwitchable }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsControl subgroup objects."
    ::= { xupsConformance 13 }

xupsConfigFullGroup  OBJECT-GROUP
    OBJECTS { xupsConfigOutputVoltage, xupsConfigInputVoltage, xupsConfigOutputWatts, 
              xupsConfigOutputFreq, xupsConfigDateAndTime, xupsConfigLowOutputVoltageLimit, 
              xupsConfigHighOutputVoltageLimit, xupsConfigInstallDate }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsConfig subgroup objects."
    ::= { xupsConformance 14 }

xupsTrapControlFullGroup  OBJECT-GROUP
    OBJECTS { xupsMaxTrapLevel, xupsSendTrapType, xupsTrapMessage, 
              xupsHeartbeatMinsInterval }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsTrapControl subgroup objects."
    ::= { xupsConformance 15 }

xupsRecepFullGroup  OBJECT-GROUP
    OBJECTS { xupsNumReceptacles, xupsRecepIndex, xupsRecepStatus, 
              xupsRecepOffDelaySecs, xupsRecepOnDelaySecs, 
              xupsRecepAutoOffDelay, xupsRecepAutoOnDelay, xupsRecepShedSecsWithRestart,
              xupsRecepHourlyPowerUsage, xupsRecepCumulativePowerUsage, xupsRecepCumulativePowerUsageTimer }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsRecep subgroup objects."
    ::= { xupsConformance 16 }

xupsTopologyFullGroup  OBJECT-GROUP
    OBJECTS { xupsTopologyType, xupsTopoMachineCode, 
              xupsTopoUnitNumber, xupsTopoPowerStrategy }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsTopology subgroup objects."
    ::= { xupsConformance 17 }

xupstdNotifyGroup NOTIFICATION-GROUP
    NOTIFICATIONS { xupstdControlOff, xupstdControlOn, xupstdOnBattery, xupstdLowBattery, 
                    xupstdUtilityPowerRestored, xupstdReturnFromLowBattery, 
                    xupstdOutputOverload, xupstdInternalFailure, xupstdBatteryDischarged, 
                    xupstdInverterFailure, xupstdOnBypass, xupstdBypassNotAvailable, 
                    xupstdOutputOff, xupstdInputFailure, xupstdBuildingAlarm, 
                    xupstdShutdownImminent, xupstdOnInverter, xupstdBreakerOpen, 
                    xupstdAlarmEntryAdded, xupstdAlarmEntryRemoved, xupstdAlarmBatteryBad, 
                    xupstdOutputOffAsRequested, xupstdDiagnosticTestFailed, 
                    xupstdCommunicationsLost, xupstdUpsShutdownPending, xupstdAlarmTempBad,
                    xupstdAlarmTestInProgress, xupstdAmbientTempBad, xupstdLossOfRedundancy,  
                    xupstdAlarmChargerFailed, xupstdAlarmFanFailure, xupstdAlarmFuseFailure, 
                    xupstdPowerSwitchBad, xupstdModuleFailure, xupstdOnAlternatePowerSource, 
                    xupstdAltPowerNotAvailable, xupstdNoticeCondition, xupstdHeartbeat, 
                    xupstdDiagnosticTestPassed, xupstdOutputBad, xupstdAwaitingPower, 
                    xupstdOnMaintenanceBypass, xupstdCommEstablished, xupstdAgentDown,
                    xupstdOutputNotProtected, xupstdTestTrap }
    STATUS  current
    DESCRIPTION
        "The Alarm and Event notifications from the xupsTrapDefined source (xupstd)."
    ::= { xupsConformance 18 }

xupstdEMPNotifyGroup NOTIFICATION-GROUP
    NOTIFICATIONS { xupstdContactActiveNotice, xupstdContactInactiveNotice, 
                    xupstdRemoteTempBad, xupstdRemoteHumidityBad  }
    STATUS  current
    DESCRIPTION
        "The EMP's Alarm and Event notifications from the xupsTrapDefined source (xupstd)."
    ::= { xupsConformance 19 }


xupsMibFullCompliance MODULE-COMPLIANCE
    STATUS     current
    DESCRIPTION
       "A compliance statement for all of everything in this MIB."
    MODULE -- this module
       MANDATORY-GROUPS  { xupsIdentFullGroup, xupsBatteryFullGroup, xupsInputFullGroup, 
                           xupsInputTableFullGroup, xupsOutputFullGroup, xupsOutputTableFullGroup, 
                           xupsBypassFullGroup, xupsEnvironmentFullGroup, xupsAlarmFullGroup, 
                           xupsAlarmEventsFullGroup, xupsTestFullGroup, xupsControlFullGroup, 
                           xupsConfigFullGroup, xupsTrapControlFullGroup, xupsRecepFullGroup, 
                           xupsTopologyFullGroup, xupstdNotifyGroup, xupstdEMPNotifyGroup,
                           xupsBypassTableFullGroup, xupsInputTotalFullGroup, xupsOutputTotalFullGroup,
                           xupsBypassTotalFullGroup }
    ::= { xupsConformance 20 }

xupsDeprecatedGroup  OBJECT-GROUP
    OBJECTS { xupsAlarmEventDateAndTime, xupsAlarmEventKind,
              xupsAlarmEventDescr, xupsControlOutputOnTrapDelay }
    STATUS  deprecated
    DESCRIPTION
        "Contains objects which are now deprecated."
    ::= { xupsConformance 21 }

xupsBypassTableFullGroup  OBJECT-GROUP
    OBJECTS { xupsBypassId, xupsBypassName, xupsBypassCurrentHighPrecision, xupsBypassWatts }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsBypassTable subgroup objects."
    ::= { xupsConformance 22 }

xupsInputTotalFullGroup  OBJECT-GROUP
    OBJECTS { xupsInputAverageVoltage, xupsInputTotalCurrent, xupsInputTotalWatts,
              xupsInputTotalVA, xupsInputAveragePowerFactor }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsInputTotal subgroup objects."
    ::= { xupsConformance 23 }

xupsOutputTotalFullGroup  OBJECT-GROUP
    OBJECTS { xupsOutputAverageVoltage, xupsOutputTotalCurrent, xupsOutputTotalWatts,
              xupsOutputTotalVA, xupsOutputAveragePowerFactor }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsOutputTotal subgroup objects."
    ::= { xupsConformance 24 }

xupsBypassTotalFullGroup  OBJECT-GROUP
    OBJECTS { xupsBypassAverageVoltage, xupsBypassTotalCurrent, xupsBypassTotalWatts,
              xupsBypassTotalVA, xupsBypassAveragePowerFactor }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsOutputTotal subgroup objects."
    ::= { xupsConformance 25 }

xupsAgentFullGroup  OBJECT-GROUP
    OBJECTS { xupsAgentManufacturer, xupsAgentModel, 
              xupsAgentSoftwareVersion, xupsAgentPartNumber, xupsAgentSerialNumber }
    STATUS  current
    DESCRIPTION
        "The Full set of xupsAgent subgroup objects."
    ::= { xupsConformance 26 }

    END