LIEBERT-GP-SRC-MIB DEFINITIONS ::= BEGIN

IMPORTS
    sysUpTime
        FROM RFC1213-MIB
    MODULE-IDENTITY,
    OBJECT-TYPE,
    Integer32,
    Unsigned32
        FROM SNMPv2-SMI
    lgpSrc,
    liebertSrcModuleReg
        FROM LIEBERT-GP-REGISTRATION-MIB
   ;

-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
liebertGlobalProductsSrcModule MODULE-IDENTITY
  LAST-UPDATED "201711100000Z"
  ORGANIZATION "Liebert Corporation"
  CONTACT-INFO
      "Contact:   Technical Support

      Postal:
      Liebert Corporation
      1050 Dearborn Drive
      P.O. Box 29186
      Columbus OH, 43229
      US

      Tel: +1 (800) 222-5877

      E-mail: liebert.monitoring@vertivco.com
      Web:    www.vertivco.com

      Author:  Colby Lin "

   DESCRIPTION
      "The MIB module used to register Liebert POWER related SNMP OIDs.

      Copyright 2008-2008 Liebert Corporation. All rights reserved.
      Reproduction of this document is authorized on the condition
      that the forgoing copyright notice is included.

      This Specification is supplied 'AS IS' and Liebert Corporation
      makes no warranty, either express or implied, as to the use,
      operation, condition, or performance of the Specification."

   REVISION "201711100000Z"
   DESCRIPTION
    "Added unknown(2147483647) for invalid SRC device readings"

   REVISION "201710160000Z"
   DESCRIPTION
    "Added Temperature High/Low Threshold"

   REVISION "201708180000Z"
   DESCRIPTION
    "Initial Version"

   ::= { liebertSrcModuleReg 1 }

lgpSrcTable OBJECT-TYPE
    SYNTAX SEQUENCE OF LgpSrcEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION "A table containing information about SRC device."
    ::= { lgpSrc 1 }

lgpSrcEntry OBJECT-TYPE
    SYNTAX      LgpSrcEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This entry defines the contents of the rows for the table
        'lgpSrcTable'.  A row in this table cannot be created or deleted by
        SNMP operations on columns of the table."
    INDEX       { lgpSrcDevId }
    ::= { lgpSrcTable 1 }

    LgpSrcEntry ::= SEQUENCE {
            lgpSrcDevId                           Unsigned32,
            lgpSrcDevAddress                      Unsigned32,
            lgpSrcDevState                        INTEGER,
            lgpSrcDevTemperatureDegF              INTEGER,
            lgpSrcDevTemperatureSetpointDegF      INTEGER,
            lgpSrcDevTemperatureDegC              INTEGER,
            lgpSrcDevTemperatureSetpointDegC      INTEGER,
            lgpSrcDevFanSpeed                     INTEGER,
            lgpSrcDevPowerStatus                  INTEGER,
            lgpSrcDevOperatingMode                INTEGER,
            lgpSrcDevTemperatureHighThresholdDegF INTEGER,
            lgpSrcDevTemperatureLowThresholdDegF  INTEGER,
            lgpSrcDevTemperatureHighThresholdDegC INTEGER,
            lgpSrcDevTemperatureLowThresholdDegC  INTEGER
            }

    lgpSrcDevId OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This value must remain constant between agent initializations.
            This Device ID is used as an index of the table
            'lgpSrcTable'."
        ::= { lgpSrcEntry 1 }

    lgpSrcDevAddress OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This value must remain constant between agent initializations.
            This Device Address is used as an index of the table
            'lgpSrcTable'."
        ::= { lgpSrcEntry 2 }

    lgpSrcDevState OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        enabled(1),
                        standbyOffline(2),
                        unavailableOffline(3),
                        absent(4)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Indicates the current state of SRC device.  The value of this
            object is set to enabled(1) if the SRC device has been enabled.
            The value of this object is set to standbyOffline(2) if the SRC
            device is waiting for an external action to activate it.  The value
            of this object is set to unavailableOffline(3) if the SRC device is
            present but cannot be used.  The value of this object is set to
            absent(4) if the SRC device is not present or not detected.  The
            value of this object will be one of the valid device state:
            enabled(1), standbyOffline(2), unavailableOffline(3), or
            absent(4)."
        ::= { lgpSrcEntry 3 }

    lgpSrcDevTemperatureDegF OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        unknown(2147483647)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured temperature value in Fahrenheit.  The value of this
            object is only vaild if the lgpSrcDevState object is set to
            enabled(1).  The value of this object will be set to
            unknown(2147483647) if the value of lgpSrcDevState object is set to
            one of the following values: standbyOffline(2),
            unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 4 }

    lgpSrcDevTemperatureSetpointDegF OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        unknown(2147483647)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The temperature setting in Fahrenheit for SRC.  This setting may
            or may not be the setting used from control.  Some systems have the
            capability to dynamically change the control setting based on
            environmental conditions and/or user configuration.  The value of
            this object is only vaild if the lgpSrcDevState object is set to
            enabled(1).  The value of this object will be set to
            unknown(2147483647) if the value of lgpSrcDevState object is set to
            one of the following values: standbyOffline(2),
            unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 5 }

    lgpSrcDevTemperatureDegC OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        unknown(2147483647)
                    }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured temperature value in Celsius.  The value of this
            object is only vaild if the lgpSrcDevState object is set to
            enabled(1).  The value of this object will be set to
            unknown(2147483647) if the value of lgpSrcDevState object is set to
            one of the following values: standbyOffline(2),
            unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 6 }

    lgpSrcDevTemperatureSetpointDegC OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        unknown(2147483647)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The temperature setting in Celsius for SRC.  This setting may or
            may not be the setting used from control.  Some systems have the
            capability to dynamically change the control setting based on
            environmental conditions and/or user configuration.  The value of
            this object is only vaild if the lgpSrcDevState object is set to
            enabled(1).  The value of this object will be set to
            unknown(2147483647) if the value of lgpSrcDevState object is set to
            one of the following values: standbyOffline(2),
            unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 7 }

    lgpSrcDevFanSpeed OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        low(1),
                        middle(2),
                        high(3),
                        auto(4),
                        unknown(2147483647)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The present fan speed of the SRC device.  This object will be one
            of the valid fan speed:  low(1), middle(2), high(3) or auto(4) if
            the value of lgpSrcDevState object is set to enabled(1).  The value
            of this object will be set to unknown(2147483647) if the value of
            lgpSrcDevState object is set to one of the following values:
            standbyOffline(2), unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 8 }

    lgpSrcDevPowerStatus OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        off(0),
                        on(1),
                        unknown(2147483647)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The value of this object specifies the power status of SRC device.
            Power status cannot be configured by an operator.  The value of
            this object is set to off(0) if the SRC device is powered off.
            The value of this object is set to on(1) if the SRC device is
            powered on.  The value of this object will be one of the valid power
            status: off(0) or on(1) if lgpSrcDevState is enabled(1).  The value
            of this object will be set to unknown(2147483647) if the value of
            lgpSrcDevState object is set to one of the following values:
            standbyOffline(2), unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 9 }

    lgpSrcDevOperatingMode OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        cooling(0),
                        dehumidify(1),
                        fan(2),
                        ai(3),
                        heating(4),
                        unknown(2147483647)
                    }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The present operating mode of the SRC device.  This object will be
            one of the valid operating mode: cooling(0), dehumidify(1), fan(2),
            ai(3) or heating(4) if the value of lgpSrcDevState object is set to
            enabled(1).  The value of this object will be set to
            unknown(2147483647) if the value of lgpSrcDevState object is set to
            one of the following values: standbyOffline(2),
            unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 10 }

    lgpSrcDevTemperatureHighThresholdDegF OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        unknown(2147483647)
                    }
        UNITS       "degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The high temperature notification threshold.  This is the maximum
            value of 'lgpSrcDevTemperatureDegF' before the agent sends a
            notification.  The value of this object is only vaild if the
            lgpSrcDevState object is set to enabled(1).  The value of this
            object will be set to unknown(2147483647) if the value of
            lgpSrcDevState object is set to one of the following values:
            standbyOffline(2), unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 11 }

    lgpSrcDevTemperatureLowThresholdDegF OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        unknown(2147483647)
                    }
        UNITS       "degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low temperature notification threshold.  This is the minimum
            value of 'lgpSrcDevTemperatureDegF' before the agent sends a
            notification.  The value of this object is only vaild if the
            lgpSrcDevState object is set to enabled(1).  The value of this
            object will be set to unknown(2147483647) if the value of
            lgpSrcDevState object is set to one of the following values:
            standbyOffline(2), unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 12 }

    lgpSrcDevTemperatureHighThresholdDegC OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        unknown(2147483647)
                    }
        UNITS       "degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The high temperature notification threshold.  This is the maximum
            value of 'lgpSrcDevTemperatureDegC' before the agent sends a
            notification.  The value of this object is only vaild if the
            lgpSrcDevState object is set to enabled(1).  The value of this
            object will be set to unknown(2147483647) if the value of
            lgpSrcDevState object is set to one of the following values:
            standbyOffline(2), unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 13 }

    lgpSrcDevTemperatureLowThresholdDegC OBJECT-TYPE
        SYNTAX      INTEGER
                    {
                        unknown(2147483647)
                    }
        UNITS       "degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The low temperature notification threshold.  This is the minimum
            value of 'lgpSrcDevTemperatureDegC' before the agent sends a
            notification.  The value of this object is only vaild if the
            lgpSrcDevState object is set to enabled(1).  The value of this
            object will be set to unknown(2147483647) if the value of
            lgpSrcDevState object is set to one of the following values:
            standbyOffline(2), unavailableOffline(3) or absent(4)."
        ::= { lgpSrcEntry 14 }
END